32 Functional description

4.1.3.Monitoring and control circuits

The monitoring and control circuits offer the following characteristics :

soft start

rectifier fail alarm ( RFA )

control for local and remote equalize ( EQL )

temporary release ( TR )

thermal shutdown ( THSD )

input ac monitoring

local and remote high voltage dc shutdown ( HVSD )

local and remote HVSD reset

fan failure detection

4.1.4.Output capacitors

The output capacitors will be completely discharged ( < 2 V ) two minutes after the ac power has been removed and the rectifier has been disconnected from the batteries or the parallel rectifiers.

4.2.Description of the front panel

4.2.1.Breakers

DC circuit breaker

A dc circuit breaker is provided to protect against current overload and to manually disconnect from the power plant.

When the breaker is in the 0 ( OFF ) position, an RFA is triggered and the remote sense leads RG+ and RC– are internally disconnected. The rectifier will continue to operate, allowing the adjustment of the FLT, EQL and HVSD set points.

AC breaker

The input ac circuit breaker can be used to locally turn the rectifier ON or OFF. The local ON / OFF control overrides any remote control signals

( for example, TR ). Putting the breaker to OFF causes an RFA to be issued and the RFA LED to light up, as long as the rectifier output is connected to batteries.

UM5C05C P0745680 Standard 6.00 October 2001

Emerson Energy Systems

Page 32
Image 32