45

5. Operation

5.1.Standard settings

The parameters of the NT5C05CA / CB / CC rectifiers are set as indicated in Table 15. For different settings refer to User Manual Voltage_level entitled Voltage Level Limits for Power Plants, Rectifiers and Controllers.

Table 15 - Standard settings for the rectifier

Parameter

Setting

Rectifier float output voltage ( FLOAT )

52.1 ±0.1 V dc

Rectifier equalize output voltage

52.8 ±0.1 V dc

( EQUALIZE )

 

Rectifier high voltage shutdown threshold

56.5 ±0.1 V dc

Rectifier output current limit

205 A ±5 A

Rectifier start delay

4 sec

Low ac input disconnect

330 ±5 V ac

Low ac input reconnect

350 ±5 V ac

 

 

High ac input disconnect

475 ±5 V ac

High ac input reconnect

460 ±5 V ac

Load sharing method

Slope

Emerson Energy Systems

Rectifier 200I/48NT5C05C Installation and User Manual

Page 45
Image 45
Emerson 200I/48-NT5C05C user manual Operation, Standard settings for the rectifier Parameter Setting