7. Troubleshooting

Table 16 - Diagnosing system faults

Fault symptom

 

Possible causes

 

 

 

The RFA LED is lit.

No ac input or input is out of bounds ( ac ON

 

 

LED is extinguished ).

 

AC Input / dc output circuit breaker is open.

 

The rectifier has received an HVSD signal from

 

 

the controller, or a TR signal is present.

 

An internal high voltage shutdown ( HVSD ) has

 

 

occurred.

 

Two cooling fans or fuses have failed.

 

The inrush fuse has blown.

 

The dc circuit breaker is open.

 

A thermal shutdown has occurred.

 

Ambient air temperature is high.

 

Air inlet / outlet air is blocked, or the air filter is

 

 

clogged.

 

A rectifier is in 'Start Time Delay' mode and the

 

 

RFA will cease when the required time delay has

 

 

elapsed.

 

Defective rectifier.

The HVSD LED is lit.

The internal high voltage shutdown point is set

 

 

to low ( below the float or equalize setting ).

 

The controller triggered a remote HVSD.

 

 

 

 

 

− continued−