Emerson manual Ordering Information, Rosemount 848L, Reference Manual

Models: 848L

1 105
Download 105 pages 39.85 Kb
Page 53
Image 53
ORDERING
Rosemount Junction Box required?

Reference Manual

00809-0100-4696, Rev AA September 2004

ORDERING

INFORMATION

Rosemount 848L

Model

Product Description (Includes One Fieldbus H1 Segment)

 

 

848L

Fieldbus Logic Transmitter

 

 

Code

Communications Protocol

 

 

FFOUNDATIONfieldbus digital signal

(includes 8 DI, 4 DO, 1 MDI, and 1 MDO function blocks, and Backup Link Active Scheduler)

Code

Power Input

 

 

 

 

A

Bus and I/O Power (4-wire)

 

 

 

 

Code

Product Certifications

 

 

 

 

NA

No Approval

No

 

 

 

N1

CENELEC ATEX Type n (enclosure required)

Yes

NC

CENELEC ATEX Type n Component

No(1)

ND

CENELEC ATEX Dust Ignition Proof

Yes

N5

FM Non-Incendive for Class 1, Division 2, Groups A, B, C, D

Yes

 

 

 

N6

CSA Non-Incendive for Class 1, Division 2, Groups A, B, C, D

Yes

N7

IECEx Type n Approval (consult factory for availability) (enclosure required)

 

 

 

 

Code

Discrete Inputs and Outputs Types

 

 

 

 

S001

8 - Dry Contact Inputs / 4 - 9 to 32 VDC Outputs

 

 

 

 

S002

8 - 2-wire NAMUR Sensor Inputs / 4 - 9 to 32 VDC Outputs

 

S003

8 - 3-wire NAMUR Sensor Inputs / 4 - 9 to 32 VDC Outputs

 

 

 

 

S004

8 - 9 to 32 VDC Inputs / 4 - 9 to 32 VDC Outputs

 

Code

Options

 

 

 

 

 

Transient Protection

 

T1

Transient Protection (Consult factory for availability)

 

 

 

 

 

Mounting Kit Options

 

B6

Mounting Kit to a 2 in. pipe

 

 

 

 

 

Non Explosion-Proof Junction Box Options

 

JP1

Plastic Junction Box; No Entries

 

 

 

JP2

Plastic Junction Box; Cable Glands (9 X M20 nickel-plated brass glands for 7.5-11.9 mm unarmored cable)

JP3

Plastic Junction Box; Conduit Entries (5 Plugged Holes, suitable for installing 1/2-in. NPT fittings)

 

JA1

Aluminum Junction Box; No Entries

 

JA2

Aluminum Cable Glands (9 X M20 nickel-plated brass glands for 7.5-11.9 mm unarmored cable)

 

 

 

 

JA3

Aluminum Conduit Entries (5 Plugged Holes, suitable for installing 1/2-in. NPT fittings)

 

JS1

Stainless Steel Junction Box; No Entries

 

 

 

 

JS2

SST Box; Cable Glands (9 X M20 nickel-plated brass glands for 7.5-11.9 mm unarmored cable)

 

JS3

Stainless Steel Box, Conduit Entries (5 Plugged Holes, suitable for installing 1/2-in. NPT fittings)

 

 

Conduit Electrical Connector

 

GE(2)

M12, 4-pin, Male Connector (eurofast®)

 

GM(2)

A size Mini, 4-pin, Male Connector (minifast®)

 

 

Software Options

 

 

 

 

CT

Disable Local Logic Function

 

 

 

 

Typical Model Number: 848L F A NA S001 T1 JP1

(1)The Rosemount 848L ordered with option code NC is not approved as a stand-alone unit. Additional system certification is required.

(2)Not available with certain hazardous location certifications. Contact a Rosemount representative for details.

A-7

Page 53
Image 53
Emerson manual Ordering Information, Rosemount 848L, Reference Manual