Rosemount 848L
Reference Manual
Table
Number Parameter | Description |
|
|
23NV_ CYCLE_T Minimum time interval specified by the manufacturer for writing copies of NV parameters to
24 | FREE_ SPACE | Percent of memory available for further configuration. Zero in preconfigured resource. |
25 | FREE_ TIME | Percent of the block processing time that is free to process additional blocks. |
|
|
|
26 | SHED_ RCAS | Time duration at which to give up on computer writes to function block RCas locations. Shed from RCas |
|
| will never happen when SHED_ RCAS = 0. |
27 | SHED_ ROUT | Time duration at which to give up on computer writes to function block ROut locations. Shed from ROut will |
|
| never happen when SHED_ ROUT = 0. |
|
|
|
28 | FAULT_ STATE | Condition set by loss of communication to an output block, fault promoted to an output block or physical |
|
| contact. When FAULT_ STATE condition is set, then output function blocks will perform their FAULT_ |
|
| STATE actions. |
29 | SET_ FSTATE | Allows the FAULT_ STATE condition to be manually initiated by selecting Set. |
|
|
|
30 | CLR_ FSTATE | Writing a Clear to this parameter will clear the device FAULT_ STATE if the field condition has cleared. |
31 | MAX_ NOTIFY | Maximum number of unconfirmed notify messages possible. |
|
|
|
32 | LIM_ NOTIFY | Maximum number of unconfirmed alert notify messages allowed. |
33 | CONFIRM_ TIME | The time the resource will wait for confirmation of receipt of a report before trying again. Retry will not |
|
| happen when CONFIRM_ TIME = 0. |
|
|
|
34 | WRITE_ LOCK | If set, no writes from anywhere are allowed, except to clear WRITE_ LOCK. Block inputs will continue to |
|
| be updated. |
35 | UPDATE_ EVT | This alert is generated by any change to the static data. |
|
|
|
36 | BLOCK_ ALM | The BLOCK_ ALM is used for all configuration, hardware, connection failure or system problems in the |
|
| block. The cause of the alert is entered in the subcode field. The first alert to become active will set the |
|
| Active status in the Status attribute. As soon as the Unreported status is cleared by the alert reporting task, |
|
| another block alert may be reported without clearing the Active status, if the subcode has changed. |
37 | ALARM_ SUM | The current alert status, unacknowledged states, unreported states, and disabled states of the alarms |
|
| associated with the function block. |
|
|
|
38 | ACK_ OPTION | Selection of whether alarms associated with the block will be automatically acknowledged. |
39 | WRITE_ PRI | Priority of the alarm generated by clearing the write lock. |
|
|
|
40 | WRITE_ ALM | This alert is generated if the write lock parameter is cleared. |
41 | ITK_ VER | Major revision number of the interoperability test case used in certifying this device as interoperable. The |
|
| format and range are controlled by the Fieldbus Foundation. |
|
|
|
42 | DISTRIBUTOR | Reserved for use as distributor ID. No Foundation enumerations defined at this time. |
43 | DEV_STRING | This is used to load new licensing into the device. The value can be written but will always read back with |
|
| a value of 0. |
|
|
|
44 | XD_ OPTIONS | Indicates which transducer block licensing options are enabled. |
45 | FB_ OPTIONS | Indicates which function block licensing options are enabled. |
|
|
|
46 | DIAG_ OPTIONS | Indicates which diagnostics licensing options are enabled. |
47 | MISC_ OPTIONS | Indicates which miscellaneous licensing options are enabled. |
|
|
|
48 | RB_ SFTWR_ | Major revision of software that the resource block was created with. |
| REV_ MAJOR |
|
49 | RB_ SFTWR_ | Minor revision of software that the resource block was created with. |
| REV_ MINOR |
|
|
|
|
50 | RB_ SFTWR_ | Build of software that the resource block was created with. |
| REV_ BUILD |
|
51 | RB_SFTWR_REV_ | The string contains the following fields: |
| ALL | Major rev: |
|
| Minor rev: |
|
| Build rev: |
|
| Time of build: 8 characters, xx:xx:xx, military time |
|
| Day of week of build: 3 characters, Sun, Mon, |
|
| Month of build: 3 characters, Jan, Feb. |
|
| Day of month of build: |
|
| Year of build: 4 characters, decimal |
|
| Builder: 7 characters, login name of builder |
|
|
|
52 | HARDWARE_ REV | Hardware revision of that hardware that has the resource block in it. |
|
|
|