Image 61
I/O TRANSDUCER

Reference Manual

00809-0100-4696, Rev AA September 2004

Rosemount 848L

I/O TRANSDUCER

PARAMETERS

Table C-2. I/O Transducer Parameters

Numbe

 

 

r

Parameter

Description

 

 

 

1

ST_ REV

The revision level of the static data associated with the function block.

 

 

 

2

TAG_ DESC

The user description of the intended application of the block.

3

STRATEGY

The strategy field can be used to identify grouping of blocks.

 

 

 

4

ALERT_ KEY

The identification number of the plant unit.

5

MODE_ BLK

The actual, target, permitted, and normal modes of the block. For further description, see the Mode

 

 

parameter formal model in FF-890.

 

 

 

6

BLOCK_ ERR

This parameter reflects the error status associated with the hardware or software components

 

 

associated with a block. Multiple errors may be shown. For a list of enumeration values, see FF-890,

 

 

Block_ Err formal model.

7

UPDATE_ EVT

This alert is generated by any change to the static data.

 

 

 

8

BLOCK_ ALM

The block alarm is used for all configuration, hardware, connection failure, or system problems in the

 

 

block. The cause of the alert is entered in the subcode field. The first alert to become active will set the

 

 

Active status in the Status attribute. As soon as the Unreported status is cleared by the alert reporting

 

 

task, another block alert may be reported without clearing the Active status, if the subcode has

 

 

changed.

9

TRANSDUCER_

A directory that specifies the number and starting indices of the transducers in the transducer block. For

 

DIRECTORY

further information, please refer to the Transducer Block Application Process - Part 1 (FF-902)

 

 

specification.

 

 

 

10

TRANSDUCER_ TYPE

Identifies the transducer that follows.

11

XD_ ERROR

One of the error codes defined in FF-903 XD_ ERROR and Block Alarm Subcodes.

 

 

 

12

COLLECTION_

A directory that specifies the number, starting indices, and DD item IDs of the data collections in each

 

DIRECTORY

transducer within a transducer block. For further information, please refer FF-902.

13

IN_ 1_ TAG

An identifier associated with discrete input 1.

 

 

 

14

IN1

The value and status of discrete input 1.

15

PULSE_ COUNT_ 1

The number of pulses that have occurred on IN1 since last reset.

 

 

 

16

IN_ 1_ CONFIG.IO_TYPE

The transducer type of discrete sensor 1.

16

IN_ 1_ CONFIG.FILTER

Any state change on IN1 that lasts for a duration less than this filter value, will be ignored by the device.

 

 

 

16

IN_ 1_ CONFIG.FAIL_

When the device detects a failure, IO1 will have its value set to this value.

 

SAFE

 

17

IN_ 2_ TAG

An identifier associated with discrete input 2.

 

 

 

18

IN2

The value and status of discrete input 2.

19

PULSE_ COUNT_ 2

The number of pulses that have occurred on IN2 since last reset.

 

 

 

20

IN_ 2_ CONFIG.IO_TYPE

The transducer type of discrete sensor 2.

20

IN_ 2_ CONFIG.FILTER

Any state change on IN2 that lasts for a duration less than this filter value, will be ignored by the device.

 

 

 

20

IN_ 2_ CONFIG.FAIL_

When the device detects a failure, IO2 will have its value set to this value.

 

SAFE

 

21

IN_ 3_ TAG

An identifier associated with discrete input 3.

 

 

 

22

IN3

The value and status of discrete input 3.

23

PULSE_ COUNT_ 3

The number of pulses that have occurred on IN3 since last reset.

 

 

 

24

IN_ 3_ CONFIG.IO_TYPE

The transducer type of discrete sensor 3.

24

IN_ 3_ CONFIG.FILTER

Any state change on IN3 that lasts for a duration less than this filter value, will be ignored by the device.

 

 

 

24

IN_ 3_ CONFIG.FAIL_

When the device detects a failure, IO3 will have its value set to this value.

 

SAFE

 

25

IN_ 4_ TAG

An identifier associated with discrete input 4.

 

 

 

26

IN4

The value and status of discrete input 4.

27

PULSE_ COUNT_ 4

The number of pulses that have occurred on IN4 since last reset.

 

 

 

28

IN_ 4_ CONFIG.IO_TYPE

The transducer type of discrete sensor 4.

28

IN_ 4_ CONFIG.FILTER

Any state change on IN4 that lasts for a duration less than this filter value, will be ignored by the device.

 

 

 

28

IN_ 4_ CONFIG.FAIL_

When the device detects a failure, IO4 will have its value set to this value.

 

SAFE

 

 

 

 