Redundant Motors - Switch on Failure

Rosemount 848L

Reference Manual

00809-0100-4696, Rev AA September 2004

Redundant Motors - Switch on Failure

Again, there are redundant pumps. There is a pressure switch in the common discharge line. If the pressure falls then the other pump is started. If the pressure does not recover, possibly because a flammable liquid is pouring on the ground from a broken pump housing, then the alternate pump is stopped. The push button controls are Stop (input 1) and Start (input 2). An auxiliary contact is required from each starter (inputs 3 and 4). The pressure switch is linked into a DO that is true when the pressure is low.

 

 

 

 

 

 

 

 