ADVISE_ ENABLE

Rosemount 848L

Reference Manual

00809-0100-4696, Rev AA September 2004

Table C-1. Resource Block Parameters

Number

Parameter

Description

 

 

 

80

ADVISE_ ENABLE

Enabled ADVISE_ ALM alarm conditions. Corresponds bit for bit to ADVISE_ ACTIVE. A bit on means that

 

 

the corresponding alarm condition is enabled and will be detected. A bit off means the corresponding

 

 

alarm condition is disabled and will not be detected.

81

ADVISE_ MASK

Mask of ADVISE_ ALM. Corresponds bit for bit to ADVISE_ ACTIVE. A bit on means that the condition is

 

 

masked out from alarming.

 

 

 

82

ADVISE_ ACTIVE

Enumerated list of advisory conditions within a device.

83

HEALTH_ INDEX

Alarm indicating advisory alarms. These conditions do not have a direct impact on the process or device

 

 

integrity.

 

 

 

84

PWA_ SIMULATE

Parameter representing the overall health of the device, 100 being perfect and 1 being non-functioning.

 

 

The value will be set based on the active PWA alarms in accordance with the requirements stated in

 

 

"Device Alerts and Health Index PlantWeb Implementation Rules". Each device may implement its own

 

 

unique mapping between the PWA parameters and HEALTH_ INDEX although a default mapping will be

 

 

available based on the following rules.

 

 

HEALTH_ INDEX will be set based on the highest priority PWA *_ ACTIVE bit as follows:

 

 

FAILED_ ACTIVE: 0 to 31 - HEALTH_ INDEX = 10

 

 

MAINT_ ACTIVE: 27 to 31 - HEALTH_ INDEX = 20

 

 

MAINT_ ACTIVE: 22 to 26 - HEALTH_ INDEX = 30

 

 

MAINT_ ACTIVE: 16 to 21 - HEALTH_ INDEX = 40

 

 

MAINT_ ACTIVE: 10 to 15 - HEALTH_ INDEX = 50

 

 

MAINT_ ACTIVE: 5 to 9 - HEALTH_ INDEX = 60

 

 

MAINT_ ACTIVE: 0 to 4 - HEALTH_ INDEX = 70

 

 

ADVISE_ ACTIVE: 16 to 31 - HEALTH_ INDEX = 80

 

 

ADVISE_ ACTIVE: 0 to 15 - HEALTH_ INDEX = 90

 

 

NONE - HEALTH_ INDEX = 100

85

ADVISE_ ACTIVE

Allows direct writes to the PlantWeb Alert "ACTIVE" parameters and RB.DETAILED_STATUS. The

 

 

simulate switch must be "ON' and the SIMULATE_STATE must be "Switch on, simulation allowed" before

 

 

PWA_SIMULATE can be active.