Open-Auto-Close

Rosemount 848L

Reference Manual

00809-0100-4696, Rev AA September 2004

Open-Auto-Close

Alarm Variations

Those applications that use a local switch with automatic control have a three position switch arranged as Open-Auto-Close. Inputs 1 and 2 are used for confirms, so input 3 is used for Open and input 4 for Closed. No input is required for Auto.

The Boolean expression is:

The 848L expression is:

EQ1 contains OR(AND(NOT(IN(4)),DO(1)),IN(3));

If there is just one close confirm on input 2, then the Boolean expression is: ALARM = TON ( ( !DO1 & !IN2 ) ( DO1 & IN2 ), TravelTime)

If there is just one open confirm on input 1, then the Boolean expression is: ALARM = TON ( ( DO1 & !IN1 ) ( !DO1 & IN1 ), TravelTime)

It both confirms are used, then the Boolean expression is: ALARM = TON ( ( !DO1 & !IN2 ) ( DO1 & !IN1 ) ( IN1 & IN2 ), TravelTime)

The equivalent 848L expressions are: TON(OR(AND(NOT(DO(1)),NOT(IN(2))),AND(DO(1),IN(2))),100);

TON(OR(AND(DO(1),NOT(IN(1)),AND(NOT(DO(1)),IN(1))),110);

TON(OR(AND(NOT(DO(1)),NOT(IN(2))),AND(DO(1),NOT(IN(1)),AND(IN(

1),IN(2))),120);

Output Variations

Output with Interlock

The chosen expression goes in the last expression used, which must be linked to a DI to generate an alarm.

A valve actuator may be spring return, requiring one output, or bistable, requiring two outputs. Output 1 is used for Open and output 2 for Close. Bistable valves often require a short pulse instead of maintained power. The

848L expressions for spring return are: OUT1 contains DO(1);

or bistable has:

OUT1 contains TP(DO(1),30); OUT2 contains TP(NOT(DO(1)),30);

The interlock may be wired, or internal, or from the bus. The example uses a DO from the bus:

OUT1 contains TP(AND(DO(1),DO(3)),30); spring return is AND(DO(1),DO(3));

OUT2 contains TP(OR(NOT(DO(1)),NOT(DO(3))),30);

F-4

Page 96
Image 96
Emerson Open-Auto-Close Alarm Variations, Output Variations Output with Interlock, Rosemount 848L, Reference Manual