Appendix C Function Blocks

Reference Manual

00809-0100-4696, Rev AA September 2004

Rosemount 848L

Appendix C Function Blocks

Resource Block Parameters

page C-1

I/O Transducer Parameters

page C-5

Logic Transducer Parameters

page C-8

Discrete Input Block

page C-9

Discrete Output Block

page C-11

Multiple Discrete Input Blocks

page C-12

Multiple Discrete Output Block

page C-13

 

 

RESOURCE BLOCK

PARAMETERS

Table C-1. Resource Block Parameters

Number

Parameter

Description

 

 

 

1

ST_ REV

The revision level of the static data associated with the function block.

 

 

 

2

TAG_ DESC

The user description of the intended application of the block.

3

STRATEGY

The strategy field can be used to identify grouping of blocks.

 

 

 

4

ALERT_ KEY

The identification number of the plant unit.

5

MODE_ BLK

The actual, target, permitted, and normal modes of the block. For further description, see the Mode

 

 

parameter formal model in FF-890.

 

 

 

6

BLOCK_ ERR

This parameter reflects the error status associated with the hardware or software components associated

 

 

with a block. Multiple errors may be shown. For a list of enumeration values, see FF-890, Block_ Err

 

 

formal model.

7

RS_ STATE

State of the function block application state machine. For a list of enumeration values, see FF-890.

 

 

 

8

TEST_ RW

Read/write test parameter - used only for conformance testing.

9

DD_ RESOURCE

String identifying the tag of the resource which contains the Device Description for the resource.

 

 

 

10

MANUFAC_ ID

Manufacturer identification number - used by an interface device to locate the DD file for the resource.

11

DEV_ TYPE

Manufacturer's model number associated with the resource - used by interface devices to locate the DD

 

 

file for the resource.

 

 

 

12

DEV_ REV

Manufacturer revision number associated with the resource - used by an interface device to locate the DD

 

 

file for the resource.

13

DD_ REV

Revision of the DD associated with the resource - used by the interface device to locate the DD file for the

 

 

resource.

 

 

 

14

GRANT_ DENY

Options for controlling access of host computer and local control panels to operating, tuning and alarm

 

 

parameters of the block.

15

HARD_ TYPES

The types of hardware available as channel numbers. The supported hardware type is: SCALAR_ INPUT

 

 

 

16

RESTART

Allows a manual restart to be initiated.

17

FEATURES

Used to show supported resource block options. The supported features are: SOFT_ WRITE_ LOCK_

 

 

SUPPORT, HARD_ WRITE_ LOCK_ SUPPORT, REPORTS, and UNICODE

 

 

 

18

FEATURE_ SEL

Used to select resource block options.

19

CYCLE_ TYPE

Identifies the block execution methods available for this resource. The supported cycle types are:

 

 

SCHEDULED, and COMPLETION_ OF_ BLOCK_ EXECUTION

 

 

 

20

CYCLE_ SEL

Used to select the block execution method for this resource.

21

MIN_ CYCLE_T

Time duration of the shortest cycle interval of which the resource is capable.

 

 

 

22

MEMORY_ SIZE

Available configuration memory in the empty resource. To be checked before attempting a download.

 

 

 

www.rosemount.com

Page 57
Image 57
Emerson manual Appendix C Function Blocks, Resource Block Parameters, Rosemount 848L, Reference Manual