TROUBLESHOOTING

Reference Manual

00809-0100-4696, Rev AA September 2004

TROUBLESHOOTING

FOUNDATION Fieldbus

Rosemount 848L

Symptom

Possible Cause

Corrective Action

 

 

 

 

 

 

Device does not show

Network configuration parameters

Set the network parameters of the LAS (host system) according to the FF

 

up in the live list

are incorrect

Communications Profile

 

 

 

 

ST: 8

 

 

 

 

MRD: 10

 

 

 

 

DLPDU PhLO: 4

 

 

 

 

MID: 7

 

 

 

 

TSC: 4 (1 ms)

 

 

 

 

T1: 1920000 (60 s)

 

 

 

 

T2: 5760000 (180 s)

 

 

 

 

T3: 480000 (15 s)

 

 

 

 

 

 

 

 

Network address is not in polled

Set first Unpolled Node and Number of UnPolled Nodes so that the device

 

 

 

range

address is within range

 

 

 

 

 

 

 

 

Power to the device is below the

Increase the power to at least 9V

 

 

 

9 VDC minimum

 

 

 

 

 

 

 

 

 

Noise on the power /

Verify terminators and power conditioners are within specification

 

 

 

communication is too high

Verify that the shield is properly terminated and not grounded at both ends. It is

 

 

 

 

best to ground the shield at the power conditioner

 

 

 

 

 

 

Device that is acting as

LAS Scheduler was not

Ensure that all of the devices that are intended to be a Backup LAS are

 

a LAS does not send

downloaded to the Backup LAS

marked to receive the LAS schedule

 

out CD

 

device

 

 

All devices go off live

 

Live list must be reconstructed by

Current link setting and configured links settings are different. Set the current

 

list and then return

Backup LAS device

link setting equal to the configured settings.

 

 

 

 

 

 

Resource Block

 

 

 

 

 

 

 

Symptom

Possible Causes

Corrective Action

 

 

 

 

 

 

Mode will not leave

Target mode not set

Set target mode to something other than OOS.

 

OOS

 

 

 

 

 

Memory Failure, Communication

BLOCK_ERR will show the lost NV Data or Lost Static Data bit set. Restart the

 

 

 

Failure, Body Temperature

device by setting RESTART to Processor. If the block error does not clear, call

 

 

 

Failure

the factory.

 

 

 

No I/O Power

Ensure power at I/O Power Terminals are between 9-32 VDC.

 

Block Alarms Will not

 

Features

FEATURE_SEL does not have Alerts enabled. Enable the report bit.

 

work

 

 

 

 

 

 

 

 

 

 

Notification

LIM_NOTIFY is not high enough. Set equal to MAX_NOTIFY.

 

 

 

 

I/O Transducer and Logic Block Troubleshooting

 

 

 

 

 

Symptom

Possible Causes

Corrective Action

 

 

 

 

 

 

Mode will not leave

Target mode not set

Set target mode to something other than OOS.

 

 

 

 

 

 

OOS

Resource block

The actual mode of the Resource block is in OOS. See Resource Block

 

 

 

 

Diagnostics for corrective action.

 

 

 

 

 

 

 

 

i/O Transducer Block

The actual mode of the Transducer Block is OOS, set it to Auto

 

 

 

 

 

 

NAMUR Sensors

 

 

 

 

 

 

 

Symptom

Possible Causes

Corrective Action

 

 

 

 

 

 

I/O Failure

Open or shorted sensor

Check sensor and wiring

 

 

 

 

 

 

4-3

Page 45
Image 45
Emerson manual Resource Block, I/O Transducer and Logic Block Troubleshooting, NAMUR Sensors, Rosemount 848L