EXAMPLES

Reference Manual

00809-0100-4696, Rev AA September 2004

Rosemount 848L

EXAMPLES

Take value of input 1 and put it on output 3.... Set OUT3_EQ to:

 

IN(1);

 

For every transition (in both directions) on input 5, send a 200 msec pulse out

 

on output 2, but only if input 2 is low.... Set OUT2_EQ to:

 

AND(OR(TP(IN(5),2),TP(NOT(IN(5)),2)),NOT(IN(2)));

 

Turn on output 1 only after input 8 has gone high 10 times, start over counting

 

when input 6 is set high.... Set OUT1_EQ to:

 

CTU(IN(8),IN(6),10);

D-5

Page 75
Image 75
Emerson manual Examples, Rosemount 848L, Reference Manual