CSB CUSTOMER INTERFACE
CAN H
CAN L
TERMINAL TB4
RTN
EXTERNAL CAN
TERMINATION
(JUMPER J40)
| TERMINAL TB5 |
| NOT USED |
| NOT USED |
| EXTERNAL EPO |
| EXTERNAL EPO RTN |
| NOT USED |
| RTN |
| TERMINAL TB7 |
| RELAY #2 RETURN |
| RELAY #2 NO |
| RELAY #2 NC |
| RELAY #1 RETURN |
| RELAY #1 NO |
| RELAY #1 NC |
| TERMINAL TB6 |
| BUILDING ALARM #1 |
| BUILDING ALARM #1 RETURN |
| BUILDING ALARM #2 |
| BUILDING ALARM #2 RETURN |
| BUILDING ALARM #3 |
| BUILDING ALARM #3 RETURN |
| BUILDING ALARM #4 |
| BUILDING ALARM #4 RETURN |
c | TERMINAL TB2 |
COMMUNICATIONS SERVER BOARD (CSB)
REFER TO DRAWING
FOR LOCATION OF CSB
NOTE: All building alarm inputs or remote features require an isolated normally open contact or switch (rated at 24 VDC, 20 mA minimum) connected between the alarm input and common terminal as shown. All control wiring and relay and switch contacts are customer provided.
NOTE: Regardless of assignment, alarms display as Building Alarm 1, Building Alarm 2, etc., on Monitor Panel. Use twisted pair wires for each alarm input and common.
| DESCRIPTION: | CUSTOMER INTERFACE WIRING | |||
|
| INSTALLATION NOTES | |||
| DRAWING NO: |
| SHEET: 2 of 5 | ||
| REVISION: G |
| DATE: | 061502 |
|
|
|
Powerware 9330 (10 | ||
| 164201300 REV. G 061502 |