Table S. Power Cable Conduit Requirements Powerware 9330 (20 kVA)
|
|
| Number of | Minimum |
| |
Powerware |
|
| Conduit | Number of | ||
Voltage | Terminal | Wires in | ||||
System | Trade Size | Conduits | ||||
|
| Conduit | ||||
|
|
| (inches) |
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
|
| AC Input to UPS | 4 | 1 | 1 | |
|
| (A, B, C, Gnd) | ||||
|
|
|
|
| ||
208 | AC Input to Bypass | 5 | 1 | 1 | ||
AC | (A, B, C, Neut, Gnd) | |||||
|
|
|
| |||
|
| Output | 5 | 1 | 1 | |
|
| (A, B, C, Neut, Gnd) | ||||
|
|
|
|
| ||
|
| AC Input to UPS | 4 | 1/2 | 1 | |
|
| (A, B, C, Gnd) | ||||
|
|
|
|
| ||
480 | AC Input to Bypass | 5 | 3/4 | 1 | ||
AC | (A, B, C, Neut, Gnd) | |||||
|
|
|
| |||
|
| Output | 5 | 3/4 | 1 | |
|
| (A, B, C, Neut, Gnd) | ||||
|
|
|
|
| ||
|
| AC Input to UPS | 4 | 1/2 | 1 | |
|
| (A, B, C, Gnd) | ||||
|
|
|
|
| ||
600 | AC Input to Bypass | 5 | 1/2 | 1 | ||
AC | (A, B, C, Neut, Gnd) | |||||
|
|
|
| |||
|
| Output | 5 | 1/2 | 1 | |
|
| (A, B, C, Neut, Gnd) | ||||
|
|
|
|
| ||
288 | External Battery DC Source | 3 | 3/4 | 1 | ||
DC | (Positive, Negative, Gnd) | |||||
|
|
|
|
|
|
| DESCRIPTION: POWER WIRING INSTALLATION NOTES |
|
|
| ||||
|
|
| DRAWING NO: |
|
| SHEET: 13 of 17 |
|
|
| |
|
|
| REVISION: F |
| DATE: | 111501 |
|
|
| |
|
|
|
|
|
|
| ||||
|
|
| ||||||||
Powerware 9330 (10 | ||||||||||
|
|
|
|
|
|
| 164201300 REV. G 061502 |