16.Output overcurrent protection and output disconnect switch are to be provided by the user. Table W lists the maximum rating for output circuit breakers satisfying the criteria for both.

Table W. Maximum Output Circuit Breaker Ratings

Powerware System

 

Output Voltage Rating

 

208V

480V

600V

 

 

 

 

 

9330---20/10

35

15

15

 

 

 

 

9330---20/15

60

25

20

 

 

 

 

9330---20/20

70

30

25

 

 

 

 

9330---40/25

90

40

30

 

 

 

 

9330---40/30

110

45

40

 

 

 

 

9330---40/35

125

60

45

 

 

 

 

9330---40/40

150

60

50

17.Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is computed at the computed voltage.

 

 

 