Installing a Remote Emergency

Power Off (EPO) Control

4.1Installation Procedures

Figure 4 ---1. Remote EPO Control

4.2To install a Remote EPO:

NOTE: Before installing a Remote EPO, be sure you have prepared the UPS according to the instructions in Chapter 2.

To install a Remote EPO control:

1.Remove cover (see Figure 4---2) from Remote EPO switch enclosure bottom.

NOTE: If mounting to a hollow wall, secure the enclosure bottom to a wood or metal stud within the wall. Do not use hollow wall anchors.

2.Securely mount the Remote EPO switch enclosure bottom. Recommended locations include operator’s consoles or by exit doors. Refer to Appendix A, Drawing 164201300---18, for enclosure dimensions and wiring knockouts.

 

 

 

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

4--1

164201300 REV. G 061502

 

 

Page 65
Image 65
Powerware 9330 Installing a Remote Emergency Power Off EPO Control, Installation Procedures, To install a Remote EPO