Table 4---1. Remote EPO Wire Terminations
From Remote | To Communications Server |
EPO Switch(s) | Board TB5 in UPS Cabinet |
|
|
TB1 | |
Use any open | |
Terminal |
|
|
|
TB2 | |
Use any open | |
Terminal |
|
|
|
Remarks
Twisted wires (2)
Table 4---2. Remote EPO
TB1
REMOTE
EPO
SWITCH (N.C.)
TB2
3
TWISTED TB5 UPS WIRES (2)
4
Remote EPO switch rating is 24 VDC, 1 Amp minimum.
NOTE: This switch must be a dedicated switch not tied into any other circuits.
7.If required, install
8.When wiring is complete, remove cover from Remote EPO switch enclosure bottom. Turn cover over and secure to enclosure bottom.
9.Secure the UPS by reversing all steps taken to prepare it for Remote EPO installation.
|
|
|
Powerware 9330 (10 | ||
164201300 REV. G 061502 |
|
|