15.4Environmental Specifications
Operating Temperature | 0 to 40˚C without derating. The recommended |
| operating temperature is 25˚C. |
|
|
Operating Altitude | Maximum 1500m (5000 ft) at 40_C without |
| derating |
|
|
Storage Temperature | |
| will cause rapid battery |
|
|
Relative Humidity (operating and | 95% maximum, noncondensing |
storage) |
|
|
|
Acoustical Noise | 60 dBA at a 1m distance |
|
|
EMI Suppression | Meets FCC Regulation 47, Part 15, for class A |
| devices |
|
|
Electrostatic Discharge (ESD) | Meets IEC |
Immunity | to 25 kV pulse without damage and with no |
| disturbance or adverse effect to the critical load. |
|
|
System Efficiency at Full Unity | 208V Models: |
Power Factor Load and Nominal | 92% in Normal Mode |
Input Voltage | 98% in High Efficiency Mode |
| 480V Models: |
| 90% in Normal Mode |
| 96% in High Efficiency Mode |
| 600V Models: |
| 90% in Normal Mode |
| 96% in High Efficiency Mode |
|
|
Powerware 9330 (10 | |
164201300 REV. G 061502 |
|