11.4System Event Messages

When a system event occurs, a message appears on the LCD screen in the UPS Status area. This message is also is written to the Active Events log and may be added to the Events History Log. The messages are divided into four categories: Alarms, Notices, Status, and Commands. The following tables contain the events displayed on the LCD System Events screen of the Control panel.

ALARMS

 

 

 

 

 

Message

Horn

Phone

Relay

Log

Indication

 

 

 

 

 

 

Battery Over Voltage

1

No

1

HA

Service Required

 

 

 

 

 

 

Battery Over Voltage OK

Off

No

1

HA

Condition Cleared

Battery Time is Low

1

No

1

HA

User Action Required

Battery Time is Low OK

Off

No

1

HA

Condition Cleared

Battery Under Voltage

1

No

1

HA

Shutdown Imminent

Battery Under Voltage OK

Off

No

1

HA

Condition Cleared

 

 

 

 

 

 

Bypass Calibration Required

1

No

1

HA

Service Required

 

 

 

 

 

 

Bypass Calibration Required OK

Off

No

1

HA

Condition Cleared

 

 

 

 

 

 

Bypass Control Failure

1

4

1

A

Service Required

 

 

 

 

 

 

Bypass Overheating Shutdown

1

No

1

HA

User Action Required

 

 

 

 

 

 

Bypass Overheating Shutdown OK

Off

No

1

HA

Condition Cleared

Bypass Overheating Warning

1

No

1

HA

Shutdown Imminent

 

 

 

 

 

 

Bypass Overheating Warning OK

Off

No

1

HA

Condition Cleared

 

 

 

 

 

 

Bypass Phase Rotation

1

No

1

HA

User Action Required

 

 

 

 

 

 

Bypass Phase Rotation OK

Off

No

1

HA

Condition Cleared

 

 

 

 

 

 

Bypass Setup Required

1

No

1

HA

Service Required

 

 

 

 

 

 

Bypass Setup Required OK

Off

No

1

HA

Condition Cleared

Calibrate DC AutoBalance

1

4

1

HA

Service Required

Calibrate DC AutoBalance OK

Off

No

1

HA

Condition Cleared

Charger Failure

1

4

1

HA

Service Required

Charger Failure OK

Off

No

1

HA

Condition Cleared

 

 

 

 

 

 

Check Battery

1

No

1

HA

User Action Required

 

 

 

 

 

 

Check Battery OK

Off

No

1

HA

Condition Cleared

 

 

 

 

 

 

Check Boost

1

4

1

HA

Service Required

Check Boost OK

Off

No

1

HA

Condition Cleared

Check CSB Setup

1

No

1

HA

Service Required

 

 

 

 

 

 

Check CSB Setup OK

Off

No

1

HA

Condition Cleared

 

 

 

 

 

 

Check Inverter

1

No

1

HA

Service Required

 

 

 

 

 

 

Check Inverter OK

Off

No

1

HA

Condition Cleared

11--2

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

 

 

164201300 REV. G 061502