Powerware 9330 Options Cabinet Installation, Joining the Options Cabinet to the UPS Cabinet

Models: 9330

1 246
Download 246 pages 17.16 Kb
Page 46
Image 46

2.4Options Cabinet Installation

2.4.1Unloading the Options Cabinet from the Pallet

To remove the Options cabinet from the pallet, refer to paragraph 2.2.1.

2.4.2Joining the Options Cabinet to the UPS Cabinet

To join the Options cabinets to the UPS, perform the following steps. Refer to Figure 2---9 for non-permanent installation or Figure 2---10 for permanent installation of the Powerware 9330 (10 kVA---20 kVA) UPS and Figure 2---11 for non-permanent installation or Figure 2---12 for permanent installation of the Powerware 9330 (25 kVA---40 kVA) UPS.

NOTE: The cables used in step 8 are coiled outside the Options cabinet and are attached at the factory to the input and output terminals of the Options cabinet.

1.Roll the Options cabinet to a spot near the left side of the UPS.

2.Remove left front solid panel, and right front vented panel from the Powerware 9330 (10 kVA---20 kVA) UPS cabinet or left front solid panel and front vented panels from Powerware 9330 (25 kVA---40 kVA) UPS cabinet. Front panels are secured with magnetic latches and are removed by pulling panels straight forward to disengage magnetic latches (see Figure 2---1 or 2---3).

3.Remove screws securing UPS cabinet internal safety shield panel and remove panel to gain access to wireway.

4.Remove front vented panel from Options cabinet. The front panel is secured with magnetic latches and are removed by pulling panels straight forward to disengage magnetic latches.

5.Remove left side outside panel from UPS cabinet. Retain hardware.

6.Remove left side panel from Options cabinet. Retain hardware.

7.Install side panel removed from the Options cabinet to the left side of the UPS cabinet. Secure with screws removed from UPS cabinet.

8.Route the input and output cables from the Options cabinet through cutout in UPS cabinet side to the UPS wireway.

9.Push the Options cabinet against the left side of the UPS cabinet.

10.If permanently mounting the system, proceed to step 16; otherwise, proceed to step 11.

11.Secure the Options cabinet in position by lowering the leveling feet, until cabinet is not resting on the casters and the cabinet is level.

12.Secure the front of Options cabinet to the front of the UPS cabinet by sliding the angle grounding/mounting bracket, from installation kit, behind the base of the Options and UPS cabinets with the bottom angle facing outward (see Figure 2---9 or 2---11). Use hardware provided in the kit to secure the bracket.

2--20

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

 

164201300 REV. G 061502

Page 46
Image 46
Powerware 9330 operation manual Options Cabinet Installation, Joining the Options Cabinet to the UPS Cabinet