Table G. INPUT/OUTPUT Ratings & External Wiring Requirements for

 

 

 

 

 

 

 

 

Powerware 9330---40/25

 

 

 

 

 

 

 

 

 

 

(Without Options Cabinet)

 

 

 

 

 

 

 

 

 

 

Ratings

 

 

 

 

 

Units

Rating 50/60 Hz

 

 

 

 

 

 

 

Basic unit ratings at

 

 

 

 

 

KVA

25

 

 

 

 

 

 

 

0.7 lagging PF load

 

 

 

 

 

KW

17.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT/OUTPUT

208

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLTAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier (0.95min.PF)

 

 

 

 

 

Amps*

70

 

 

 

 

 

 

 

AC

3 , 1 gnd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

Minimum conductor size (number per )

 

 

A

 

AWG or kcmil(ea)

3 (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*(Maximum amps includes full load current plus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

battery recharge current)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Module Bypass (UPS Bypass)

 

 

 

Amps

69.4

 

 

 

 

 

 

 

AC

Full Load Current 3 , (1) Neutral, (1) gnd

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

Minimum conductor size (number per )

 

 

 

 

AWG or kcmil(ea)

4 (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC

DC Input from External Battery Source to UPS

C

 

 

VDC (Nominal)

288

 

 

 

 

 

 

 

(1) positive, (1) negative, (1) gnd

 

 

 

 

Amps

64

 

 

 

 

 

 

 

INPUT

Minimum conductor size (number per pole)

(See note 8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWG or kcmil(ea)

4 (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC

AC Output to Critical Load

 

 

D

 

 

Amps

69.4

 

 

 

 

 

 

 

Full Load Current 3 , (1) Neutral, (1) gnd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT

 

 

 

 

AWG or kcmil(ea)

4 (1)

 

 

 

 

 

 

 

Minimum conductor size (number per )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table H. INPUT/OUTPUT Ratings & External Wiring Requirements for

 

 

 

 

 

 

 

 

Powerware 9330---40/30

 

 

 

 

 

 

 

 

 

 

(Without Options Cabinet)

 

 

 

 

 

 

 

 

 

 

Ratings

 

 

 

 

 

Units

Rating 50/60 Hz

 

 

 

 

 

 

 

Basic unit ratings at

 

 

 

 

 

KVA

30

 

 

 

 

 

 

 

0.7 lagging PF load

 

 

 

 

 

KW

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT/OUTPUT

208

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLTAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier (0.95min.PF)

 

 

 

 

 

Amps*

80

 

 

 

 

 

 

 

AC

3 , 1 gnd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

Minimum conductor size (number per )

 

 

A

 

AWG or kcmil(ea)

3 (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*(Maximum amps includes full load current plus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

battery recharge current)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Module Bypass (UPS Bypass)

 

 

 

Amps

83

 

 

 

 

 

 

 

AC

Full Load Current 3 , (1) Neutral, (1) gnd

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

Minimum conductor size (number per )

 

 

 

 

AWG or kcmil(ea)

2 (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC

DC Input from External Battery Source to UPS

C

 

 

VDC (Nominal)

288

 

 

 

 

 

 

 

(1) positive, (1) negative, (1) gnd

 

 

 

 

Amps

78

 

 

 

 

 

 

 

INPUT

Minimum conductor size (number per pole)

(See note 8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWG or kcmil(ea)

3 (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC

AC Output to Critical Load

 

 

D

 

 

Amps

83

 

 

 

 

 

 

 

Full Load Current 3 , (1) Neutral, (1) gnd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT

 

 

 

 

AWG or kcmil(ea)

2 (1)

 

 

 

 

 

 

 

Minimum conductor size (number per )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Callout letter , , , and

 

DESCRIPTION:

POWER WIRING INSTALLATION NOTES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

map to drawing #164201300---6

 

DRAWING NO:

164201300---1

 

SHEET: 5 of 17

 

 

 

 

 

 

 

 

 

REVISION:

D

 

DATE:

053001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A---6

 

 

 

 

 

 

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

 

 

 

 

 

 

 

 

 

 

 

 

164201300 REV. G 061502

Page 176