| Table B. INPUT/OUTPUT Ratings & External Wiring Requirements for |
|
|
| |||||||||
|
|
|
| Powerware |
|
|
|
|
|
| ||||||
|
|
|
| (Without Options Cabinet) |
|
|
|
|
|
| ||||||
|
|
|
| Ratings |
|
|
|
| Units |
| Rating 50/60 Hz |
|
|
| ||
|
|
| Basic unit ratings at |
|
|
|
| KVA |
| 15 |
|
|
| |||
|
|
| 0.7 lagging PF load |
|
|
|
| KW |
| 10.5 |
|
|
| |||
|
|
|
|
|
|
|
|
| INPUT/OUTPUT |
| 208 |
|
|
| ||
|
|
|
|
|
|
|
|
| VOLTAGE |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| AC Input to UPS Rectifier (0.95min.PF) |
|
| Amps* |
| 40 |
|
|
| ||||
|
|
| AC | 3 , 1 gnd |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| INPUT | Minimum conductor size (number per | ) |
| A |
| AWG or kcmil(ea) |
| 8 (1) |
|
|
| ||
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
| *(Maximum amps includes full load current plus |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| battery recharge current) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| AC Input to Module Bypass (UPS Bypass) |
|
| Amps |
| 41.6 |
|
|
| ||||
|
|
| AC | Full Load Current 3 , (1) Neutral, (1) gnd | B |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
| INPUT | Minimum conductor size (number per | ) |
|
| AWG or kcmil(ea) |
| 6 (1) |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
| DC | DC Input from External Battery Source to UPS | C |
| VDC (Nominal) |
| 288 |
|
|
| ||||
|
|
| (1) positive, (1) negative, (1) gnd |
|
|
| Amps |
| 39 |
|
|
| ||||
|
|
| INPUT | Minimum conductor size (number per pole) (See note 8) |
|
|
|
|
|
|
|
|
| |||
|
|
|
| AWG or kcmil(ea) |
| 8 (1) |
|
|
| |||||||
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| AC | AC Output to Critical Load |
|
| D |
| Amps |
| 41.6 |
|
|
| ||
|
|
| Full Load Current 3 , (1) Neutral, (1) gnd |
|
|
|
|
|
|
|
|
| ||||
|
|
| OUTPUT |
| AWG or kcmil(ea) |
| 6 (1) |
|
|
| ||||||
|
|
| Minimum conductor size (number per | ) |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| ||||||||||
|
|
|
| Table C. INPUT/OUTPUT Ratings & External Wiring Requirements for |
|
|
| |||||||||
|
|
|
| Powerware |
|
|
|
|
|
| ||||||
|
|
|
| (Without Options Cabinet) |
|
|
|
|
|
| ||||||
|
|
|
| Ratings |
|
|
|
| Units |
| Rating 50/60 Hz |
|
|
| ||
|
|
| Basic unit ratings at |
|
|
|
| KVA |
| 20 |
|
|
| |||
|
|
| 0.7 lagging PF load |
|
|
|
| KW |
| 14 |
|
|
| |||
|
|
|
|
|
|
|
|
| INPUT/OUTPUT |
| 208 |
|
|
| ||
|
|
|
|
|
|
|
|
| VOLTAGE |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| AC Input to UPS Rectifier (0.95min.PF) |
|
| Amps* |
| 52 |
|
|
| ||||
|
|
| AC | 3 , 1 gnd |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| INPUT | Minimum conductor size (number per | ) |
| A |
| AWG or kcmil(ea) |
| 6 (1) |
|
|
| ||
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
| *(Maximum amps includes full load current plus |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| battery recharge current) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| AC Input to Module Bypass (UPS Bypass) |
|
| Amps |
| 55.5 |
|
|
| ||||
|
|
| AC | Full Load Current 3 , (1) Neutral, (1) gnd | B |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
| INPUT | Minimum conductor size (number per | ) |
|
| AWG or kcmil(ea) |
| 4 (1) |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
| DC | DC Input from External Battery Source to UPS | C |
| VDC (Nominal) |
| 288 |
|
|
| ||||
|
|
| (1) positive, (1) negative, (1) gnd |
|
|
| Amps |
| 52 |
|
|
| ||||
|
|
| INPUT | Minimum conductor size (number per pole) (See note 8) |
|
|
|
|
|
|
|
|
| |||
|
|
|
| AWG or kcmil(ea) |
| 6 (1) |
|
|
| |||||||
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| AC | AC Output to Critical Load |
|
| D |
| Amps |
| 55.5 |
|
|
| ||
|
|
| Full Load Current 3 , (1) Neutral, (1) gnd |
|
|
|
|
|
|
|
|
| ||||
|
|
| OUTPUT |
| AWG or kcmil(ea) |
| 4 (1) |
|
|
| ||||||
|
|
| Minimum conductor size (number per | ) |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| NOTE: Callout letter , , , and |
| DESCRIPTION: POWER WIRING INSTALLATION NOTES |
|
| ||||||||||
|
|
| map to drawing |
| DRAWING NO: |
| SHEET: 2 of 17 |
|
| |||||||
|
|
|
|
|
| REVISION: | E |
| DATE: | 071501 |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||