Table U. Power Cable Conduit Requirements Powerware 9330 (35 kVA --40 kVA)

 

 

 

 

 

 

 

 

 

 

 

Number of

 

Minimum

 

 

 

 

 

 

 

 

Powerware

 

 

 

 

Conduit

Number of

 

 

 

 

 

 

 

Voltage

Terminal

Wires in

 

 

 

 

 

 

 

 

System

 

Trade Size

Conduits

 

 

 

 

 

 

 

 

 

 

Conduit

 

 

 

 

 

 

 

 

 

 

 

 

 

(inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

4

 

1-1/4

1

 

 

 

 

 

 

 

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9330-40/35

208

AC Input to Bypass

5

 

2

1

 

 

 

 

 

 

 

AC

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

5

 

2

1

 

 

 

 

 

 

 

 

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

4

 

1

1

 

 

 

 

 

 

 

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9330---40/35

480

AC Input to Bypass

5

 

1

1

 

 

 

 

 

 

 

AC

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

5

 

1

1

 

 

 

 

 

 

 

 

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

4

 

3/4

1

 

 

 

 

 

 

 

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9330---40/35

600

AC Input to Bypass

5

 

3/4

1

 

 

 

 

 

 

 

AC

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

N/A

 

N/A

N/A

 

 

 

 

 

 

 

 

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9330---40/35

288

External Battery DC Source

3

 

1

1

 

 

 

 

 

 

 

DC

(Positive, Negative, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

4

 

1-1/2

1

 

 

 

 

 

 

 

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9330-40/40

208

AC Input to Bypass

5

 

2

1

 

 

 

 

 

 

 

AC

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

5

 

2

1

 

 

 

 

 

 

 

 

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

4

 

3/4

1

 

 

 

 

 

 

 

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9330-40/40

480

AC Input to Bypass

5

 

1

1

 

 

 

 

 

 

 

AC

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

5

 

1

1

 

 

 

 

 

 

 

 

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

4

 

3/4

1

 

 

 

 

 

 

 

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9330-40/40

600

AC Input to Bypass

5

 

3/4

1

 

 

 

 

 

 

 

AC

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

N/A

 

N/A

N/A

 

 

 

 

 

 

 

 

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9330---40/40

288

External Battery DC Source

3

 

1-1/4

1

 

 

 

 

 

 

 

DC

(Positive, Negative, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

 

 

 

 

 

 

 

 

DRAWING NO:

164201300---1

SHEET: 15 of 17

 

 

 

 

 

 

 

 

 

REVISION: F

 

 

DATE: 111501

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A---16

 

 

 

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

 

 

 

 

 

 

 

 

 

 

164201300 REV. G 061502

Page 186
Image 186
Powerware 9330 operation manual Sheet 15