12.5 Terminal Mode
In Terminal Mode, the user can request the following:
NOTE: The brackets ([ ]) in the following bullets indicate standard keyboard characters.
To use a key combination, hold down the Escape key and press the indicated letter key.
·Display UPS Control Panel by pressing and holding [ESC], then press [V].
·Display Event History by pressing and holding [ESC], then press [H].
·Display Node Bits Setup by pressing and holding [ESC], then press [N].
·Display any new event by pressing and holding [ESC], then press [L].
12.5.1 Display UPS Control Panel
When this function is invoked, a facsimile of the UPS Control Panel is displayed on the terminal screen. All controls are functional and will control the UPS remotely. The only exception is the Load Off control which requires the operator to press and hold the local control for two seconds to shutdown the UPS.
To remotely control the UPS or view UPS information, use the escape key legend to control the function normally controlled by the Control Panel softkeys. Refer to Chapter 8 “Using the Control Panel” for instructions on navigating the control panel.
Figures 12---2 through 12---17 show the typical screens using this function.
Figure 12 ---2. Main Screen --- UPS Normal Mimic
Powerware 9330 (10 | |
164201300 REV. G 061502 |
|