Product Specifications

15.1Model Numbers

The UPS systems are housed in freestanding, cabinets with safety shields behind the front panels. The UPS systems are available in 50/60 Hz with various output power ratings. Smaller models within a system may be upgraded in the field to larger models:

System

Models

Nominal Frequency

Powerware 9330

10, 15,

20 kVA

50/60 Hz

Powerware 9330

25, 30,

35, 40 kVA

50/60 Hz

The following sections detail the input, output, environmental, and battery specifications for the UPS.

15.2UPS System Input

Operating Input

600

VAC for operation from 510 VAC to 660 VAC (50/60 Hz)

Voltage

480

VAC for operation from 408 VAC to 528 VAC (50/60 Hz)

(Nominal +10/-- 15%)

208

VAC for operation from 177 VAC to 229 VAC (50/60 Hz)

 

 

Operating Input

3 Hz of nominal (50 Hz or 60 Hz)

Frequency Range

 

 

 

 

Operating Input

Refer to Appendix A, Tables A through F, for 10, 15, and 20 kVA

Current

Models and Tables G through M, for 25, 30, 35, and 40 kVA

 

Models.

 

Reduced for Generator:

 

Adjustable

 

 

Battery Charge

Battery Charge:

Current

Up to 7 Amperes for 10, 15, and 20 kVA models

 

Up to 14 Amperes for 25, 30, 35, and 40 kVA models

 

 

Input Current

10% THD at full load (with input filter option installed)

Harmonic Content

30% THD at full load (without input filter option installed)

 

 

Power Factor

Minimum 0.96

 

 

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801---4

 

 

 

Battery Voltage

288

VDC nominal

 

(144 cells @2V/cell)

 

 

 

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

15--1

164201300 REV. G 061502

 