Product Specifications
15.1Model Numbers
The UPS systems are housed in freestanding, cabinets with safety shields behind the front panels. The UPS systems are available in 50/60 Hz with various output power ratings. Smaller models within a system may be upgraded in the field to larger models:
System | Models | Nominal Frequency | |
Powerware 9330 | 10, 15, | 20 kVA | 50/60 Hz |
Powerware 9330 | 25, 30, | 35, 40 kVA | 50/60 Hz |
The following sections detail the input, output, environmental, and battery specifications for the UPS.
15.2UPS System Input
Operating Input | 600 | VAC for operation from 510 VAC to 660 VAC (50/60 Hz) |
Voltage | 480 | VAC for operation from 408 VAC to 528 VAC (50/60 Hz) |
(Nominal | 208 | VAC for operation from 177 VAC to 229 VAC (50/60 Hz) |
|
| |
Operating Input | 3 Hz of nominal (50 Hz or 60 Hz) | |
Frequency Range |
|
|
|
| |
Operating Input | Refer to Appendix A, Tables A through F, for 10, 15, and 20 kVA | |
Current | Models and Tables G through M, for 25, 30, 35, and 40 kVA | |
| Models. | |
| Reduced for Generator: | |
| Adjustable | |
|
| |
Battery Charge | Battery Charge: | |
Current | Up to 7 Amperes for 10, 15, and 20 kVA models | |
| Up to 14 Amperes for 25, 30, 35, and 40 kVA models | |
|
| |
Input Current | 10% THD at full load (with input filter option installed) | |
Harmonic Content | 30% THD at full load (without input filter option installed) | |
|
| |
Power Factor | Minimum 0.96 | |
|
| |
Line Surges | 6 kV OC, 3 kA SC per ANSI 62.41 and IEC | |
|
|
|
Battery Voltage | 288 | VDC nominal |
| (144 cells @2V/cell) | |
|
|
|
Powerware 9330 (10 | |