Powerware 9330 operation manual Configuring the Modem, Basic Modem Configuration

Models: 9330

1 246
Download 246 pages 17.16 Kb
Page 158
Image 158

13.5Configuring the Modem

The modem must be programmed with the Call Out telephone numbers in order to operate the Remote Notification option.

To configure the modem, connect the serial port of a standard PC computer to the modem through the serial cable. Run a terminal emulation program on the computer. Test the connection to the modem by typing [A], [T] and [ENTER].

The modem should respond with either “OK” or “0” (zero). If the modem does not respond, consult the modem manufacturer’s manual to confirm your setup. If the modem still does not respond, then seek technical assistance from your modem manufacturer.

After connection, perform “Basic Modem Configuration” and the remaining sections of this chapter.

13.5.1 Basic Modem Configuration

The basic modem should be a plug and play type. All setup is done by the UPS. Only the initial phone number needs to be entered by the user.

13.5.2 Configuring the Modem to Call a Remote Computer

To configure the modem to call a remote computer, perform the following procedure:

NOTE: The brackets ([ ]) in the following steps indicate characters that require keying in prior to pressing [ENTER].

1.Connect the modem to the PC through the serial port as described in the modem manufacturer’s manual .

2.Key in [A], [T], then press [ENTER].

3.Confirm that the modem responds with “OK” or “0” (zero).

NOTE: In steps 4 through 7, the “xxxxxxx” is the phone number of a remote computer. The phone number should include all local line and long distance access numbers needed to dial out. This number is limited to 32 characters. For example, use “9” if needed for an outside line, “1” for long distance + (Area Code) + Number or whatever access codes are needed to dial the call directly. Add a “,” in the number anywhere that a delay is needed. This will cause a two-second delay. More than one delay may be added to the number; for example, enter “AT&Z0=T,9,,1 (Area Code) (Phone Number)”.

4.To program a group one number, key in [A], [T], [&], [Z], [0] (zero), [=], [xxxxxxx], then press [ENTER].

5.To program a group two number, key in [A], [T], [&], [Z], [1], [=], [xxxxxxx], then press [ENTER].

6.To program a group three number, key in [A], [T], [&], [Z], [2], [=], [xxxxxxx], then press [ENTER].

13--6

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

 

164201300 REV. G 061502

Page 158
Image 158
Powerware 9330 operation manual Basic Modem Configuration, Configuring the Modem to Call a Remote Computer