10.Per NEC article
11.Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG ground conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed in table R. All 9330 products can accommodate a double size neutral.
12.Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW,
Table R. Power Cable Conduit Requirements Powerware 9330 (10 kVA
|
|
| Number of | Minimum |
| |
Powerware |
|
| Conduit | Number of | ||
Voltage | Terminal | Wires in | ||||
System | Trade Size | Conduits | ||||
|
| Conduit | ||||
|
|
| (inches) |
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
|
| AC Input to UPS | 4 | 1/2 | 1 | |
|
| (A, B, C, Gnd) | ||||
|
|
|
|
| ||
208 | AC Input to Bypass | 5 | 3/4 | 1 | ||
AC | (A, B, C, Neut, Gnd) | |||||
|
|
|
| |||
|
| Output | 5 | 3/4 | 1 | |
|
| (A, B, C, Neut, Gnd) | ||||
|
|
|
|
| ||
|
| AC Input to UPS | 4 | 1/2 | 1 | |
|
| (A, B, C, Gnd) | ||||
|
|
|
|
| ||
480/600 | AC Input to Bypass | 5 | 1/2 | 1 | ||
AC | (A, B, C, Neut, Gnd) | |||||
|
|
|
| |||
|
| Output | 5 | 1/2 | 1 | |
|
| (A, B, C, Neut, Gnd) | ||||
|
|
|
|
| ||
288 | External Battery DC Source | 3 | 1/2 | 1 | ||
DC | (Positive, Negative, Gnd) | |||||
|
|
|
| |||
|
| AC Input to UPS | 4 | 1/2 | 1 | |
|
| (A, B, C, Gnd) | ||||
| 208/480 |
|
|
| ||
| AC Input to Bypass | 5 | 3/4 | 1 | ||
/600 | ||||||
(A, B, C, Neut, Gnd) | ||||||
| AC |
|
|
| ||
|
|
|
|
| ||
| Output | 5 | 3/4 | 1 | ||
|
| |||||
|
| (A, B, C, Neut, Gnd) | ||||
|
|
|
|
| ||
|
|
|
|
|
| |
288 | External Battery DC Source | 3 | 1/2 | 1 | ||
DC | (Positive, Negative, Gnd) | |||||
|
|
|
|
|
|
| DESCRIPTION: POWER WIRING INSTALLATION NOTES |
|
| ||||
|
|
| DRAWING NO: |
| SHEET: 12 of 17 |
|
| ||
|
|
| REVISION: F |
| DATE: | 111501 |
|
| |
|
|
|
|
|
|
| |||
|
|
|
|
| |||||
Powerware 9330 (10 |
|
|
| ||||||
164201300 REV. G 061502 |
|
|
|
|
|
|