| Table I. INPUT/OUTPUT Ratings & External Wiring Requirements for |
|
|
| |||||||||
|
|
|
| Powerware |
|
|
|
|
| |||||||
|
|
|
| (Without Options Cabinet) |
|
|
|
|
| |||||||
|
|
|
| Ratings |
|
|
|
|
| Units | Rating 50/60 Hz |
|
|
| ||
|
|
| Basic unit ratings at |
|
|
|
|
| KVA | 35 |
|
|
| |||
|
|
| 0.7 lagging PF load |
|
|
|
|
| KW | 24.5 |
|
|
| |||
|
|
|
|
|
|
|
|
|
| INPUT/OUTPUT | 208 |
|
|
| ||
|
|
|
|
|
|
|
|
|
| VOLTAGE |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| AC Input to UPS Rectifier (0.95min.PF) |
|
|
|
|
| Amps* | 92 |
|
|
| ||
|
|
| AC | 3 , 1 gnd |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| INPUT | Minimum conductor size (number per ) |
|
| A |
| AWG or kcmil(ea) | 2 (1) |
|
|
| |||
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
| *(Maximum amps includes full load current plus |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| battery recharge current) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| AC Input to Module Bypass (UPS Bypass) |
|
|
| Amps | 97 |
|
|
| ||||
|
|
| AC | Full Load Current 3 , (1) Neutral, (1) gnd |
|
| B |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
| INPUT | Minimum conductor size (number per ) |
|
|
|
| AWG or kcmil(ea) | 1 (1) |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
| DC | DC Input from External Battery Source to UPS | C |
|
| VDC (Nominal) | 288 |
|
|
| ||||
|
|
| (1) positive, (1) negative, (1) gnd |
|
|
|
| Amps | 91 |
|
|
| ||||
|
|
| INPUT | Minimum conductor size (number per pole) | (See note 8) |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| AWG or kcmil(ea) | 2 (1) |
|
|
| |||||||
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| AC | AC Output to Critical Load |
|
| D |
|
| Amps | 97 |
|
|
| ||
|
|
| Full Load Current 3 , (1) Neutral, (1) gnd |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| OUTPUT |
|
|
|
| AWG or kcmil(ea) | 1 (1) |
|
|
| ||||
|
|
| Minimum conductor size (number per ) |
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| ||||||||||
|
|
|
| Table J. INPUT/OUTPUT Ratings & External Wiring Requirements for |
|
|
| |||||||||
|
|
|
| Powerware |
|
|
|
|
| |||||||
|
|
|
| (Without Options Cabinet) |
|
|
|
|
| |||||||
|
|
|
| Ratings |
|
|
|
|
| Units | Rating 50/60 Hz |
|
|
| ||
|
|
| Basic unit ratings at |
|
|
|
|
| KVA | 40 |
|
|
| |||
|
|
| 0.7 lagging PF load |
|
|
|
|
| KW | 28 |
|
|
| |||
|
|
|
|
|
|
|
|
|
| INPUT/OUTPUT | 208 |
|
|
| ||
|
|
|
|
|
|
|
|
|
| VOLTAGE |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| AC Input to UPS Rectifier (0.95min.PF) |
|
|
|
|
| Amps* | 100 |
|
|
| ||
|
|
| AC | 3 , 1 gnd |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| INPUT | Minimum conductor size (number per ) |
|
| A |
| AWG or kcmil(ea) | 1 (1) |
|
|
| |||
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
| *(Maximum amps includes full load current plus |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| battery recharge current) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| AC Input to Module Bypass (UPS Bypass) |
|
|
| Amps | 111 |
|
|
| ||||
|
|
| AC | Full Load Current 3 , (1) Neutral, (1) gnd |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| B |
|
|
|
|
|
|
|
|
| ||
|
|
| INPUT | Minimum conductor size (number per ) |
|
|
|
| AWG or kcmil(ea) | 2/0 (1) |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
| DC | DC Input from External Battery Source to UPS | C |
|
| VDC (Nominal) | 288 |
|
|
| ||||
|
|
| (1) positive, (1) negative, (1) gnd |
|
|
|
| Amps | 100 |
|
|
| ||||
|
|
| INPUT | Minimum conductor size (number per pole) | (See note 8) |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| AWG or kcmil(ea) | 1 (1) |
|
|
| |||||||
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| AC | AC Output to Critical Load |
|
| D |
|
| Amps | 111 |
|
|
| ||
|
|
| Full Load Current 3 , (1) Neutral, (1) gnd |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| OUTPUT |
|
|
|
| AWG or kcmil(ea) | 2/0 (1) |
|
|
| ||||
|
|
|
| Minimum conductor size (number per ) |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| NOTE: Callout letter , , , and |
| DESCRIPTION: | POWER WIRING INSTALLATION NOTES |
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
| map to drawing |
| DRAWING NO: |
| SHEET: 6 of 17 |
|
| |||||||
|
|
|
|
|
| REVISION: | G |
| DATE: | 061502 |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Powerware 9330 (10 |
|
|
|
|
|
|
|
|
|
| ||||||
164201300 REV. G 061502 |
|
|
|
|
|
|
|
|
|
|
|
|