3.The Remote EPO feature opens all breakers and contactors in the UPS cabinet and isolates power from your critical load. Local electrical codes may also require tripping upstream protective devices to the UPS.
Table Z Remote EPO
TB1
REMOTE
EPO
SWITCH (N.C.)
TB2
3
TWISTED TB5 UPS WIRES (2)
4
Remote EPO switch rating is 24 VDC, 1 Amp minimum.
NOTE: This switch must be a dedicated switch not tied into any other circuits.