Installing the UPS System
2.1Preliminary Installation Information
WARNING:
Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
·Refer to Appendix A of this manual for installation drawings and additional installation notes.
·Dimensions in this manual are in millimeters and inches.
·Do not tilt the cabinets more than 10˚ during installation.
·The conduit landing plates are to be removed to add conduit landing holes as required. Plate material is 16 gauge steel (0.060 in. thick).
·The cabinets must be installed on a level floor suitable for computer or electronic equipment.
·If perforated floor tiles are required for ventilation, place them in front of the UPS. Refer to Table AA in Appendix A for equipment weight and point loading.
·Details about control wiring are provided in each procedure for connecting options and features. Drawing
|
|
|
Powerware 9330 (10 | ||
164201300 REV. G 061502 |
|
|