Powerware 9330 Table AA. Equipment Weight, Description Physical Features and Requirements

Models: 9330

1 246
Download 246 pages 17.16 Kb
Page 194
Image 194

1.The UPS equipment operating environment must meet the size and weight requirements shown in Table AA, according to your UPS system configuration.

2.In the UPS system, the UPS, Options, and Battery cabinets are palleted separately for shipping.

3.Do not tilt cabinets more than 10˚ during handling.

4.Dimensions are in millimeters (inches).

 

 

 

Table AA. Equipment Weight

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight

 

 

 

 

 

 

 

 

 

 

 

Component

 

 

 

 

Kg (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shipping

Installed

Point Loading

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Cabinet with Filter and Batteries

 

 

 

461 (1017)

435 (958)

6 at 73 (160)

 

 

 

 

 

 

 

Powerware 9330 (10 kVA---20 kVA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Cabinet with Filter and Batteries

 

 

 

873 (1925)

838 (1847)

9 at 93 (205)

 

 

 

 

 

 

 

Powerware 9330 (25 kVA---40 kVA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options Cabinet with PDM and no transformer

 

118 (260)

90 (200)

4 at 23 (50)

 

 

 

 

 

 

 

Powerware 9330 (10 kVA---20 kVA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options Cabinet with PDM and 1 transformer

 

240 (530)

213 (470)

4 at 53 (118)

 

 

 

 

 

 

 

Powerware 9330 (10 kVA---20 kVA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options Cabinet with PDM and 2 transformers

 

358 (790)

331 (730)

4 at 83 (183)

 

 

 

 

 

 

 

Powerware 9330 (10 kVA---20 kVA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options Cabinet with PDM and no transformer

 

154 (340)

120 (265)

6 at 20 (44)

 

 

 

 

 

 

 

Powerware 9330 (25 kVA---40 kVA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options Cabinet with PDM and 1 transformer

 

471 (1040)

437 (965)

6 at 73 (161)

 

 

 

 

 

 

 

Powerware 9330 (25 kVA---40 kVA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options Cabinet with PDM and 2 transformers

 

782 (1725)

748 (1650)

6 at 125 (275)

 

 

 

 

 

 

 

Powerware 9330 (25 kVA---40 kVA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery Cabinet

 

 

 

361 (795)

333 (735)

6 at 56 (123)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware 9330 (10 kVA---20 kVA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. For UPS Cabinet without Filter, subtract 25 Kg (55 lb).

 

 

 

 

 

 

 

 

 

 

 

2. For UPS Cabinet without Batteries, subtract 227 Kg (499 lb)

 

 

 

 

 

 

 

 

 

 

 

3. For Options Cabinet without PDM, subtract 11 Kg (25 lb)

 

 

 

 

 

 

 

 

 

 

 

Powerware 9330 (25 kVA---40 kVA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. For UPS Cabinet without Filter, subtract 41 Kg (90 lb).

 

 

 

 

 

 

 

 

 

 

 

2. For UPS Cabinet without Batteries, subtract 453 Kg (998 lb)

 

 

 

 

 

 

 

 

 

 

 

3. For Options Cabinet without PDM, subtract 11 Kg (25 lb)

 

 

 

 

 

 

 

 

 

5. The clearances required around the UPS System are shown in Table AB.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table AB. System Clearances

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

From Front of Cabinet

 

36 inches working space

 

 

 

 

 

 

 

 

 

 

 

From Back of Cabinet

 

12 inches air circulation clearance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

From Sides of Cabinet

 

Allow space for Options and Battery Cabinets

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION: PHYSICAL FEATURES AND REQUIREMENTS

 

 

 

 

 

 

 

 

DRAWING NO:

164201300---3

 

SHEET:

1 of 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REVISION:

G

 

DATE: 061502

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A---24

 

 

 

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

 

 

 

 

 

 

 

 

 

 

 

164201300 REV. G 061502

Page 194
Image 194
Powerware 9330 operation manual Table AA. Equipment Weight, Description Physical Features and Requirements