Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9330---20/10
(Without Options Cabinet)
| Ratings |
| Units | Rating 50/60 Hz | |
Basic unit ratings at |
| KVA | 10 | ||
0.7 lagging PF load |
| KW | 7 | ||
|
|
| INPUT/OUTPUT | 208 | |
|
|
| VOLTAGE | ||
|
|
|
| ||
| AC Input to UPS Rectifier (0.95min.PF) |
| Amps* | 28 | |
AC | 3 , 1 gnd |
| |||
|
|
| |||
INPUT | Minimum conductor size (number per ) | A | AWG or kcmil(ea) | 8 (1) | |
| |||||
| *(Maximum amps includes full load current plus |
|
|
| |
| battery recharge current) |
|
|
| |
| AC Input to Module Bypass (UPS Bypass) |
| Amps | 27.8 | |
AC | Full Load Current 3 , (1) Neutral, (1) gnd | B |
| ||
|
| ||||
INPUT | Minimum conductor size (number per ) | AWG or kcmil(ea) | 8 (1) | ||
|
| ||||
|
|
|
| ||
DC | DC Input from External Battery Source to UPS | C | VDC (Nominal) | 288 | |
(1) positive, (1) negative, (1) gnd | Amps | 26 | |||
INPUT | Minimum conductor size (number per pole) (See note 8) | AWG or kcmil(ea) | 10 (1) | ||
| |||||
AC | AC Output to Critical Load | D | Amps | 27.8 | |
Full Load Current 3 , (1) Neutral, (1) gnd |
|
| |||
OUTPUT | AWG or kcmil(ea) | 8 (1) | |||
Minimum conductor size (number per ) |
|
Read and understand the following notes while planning your installation:
1.Refer to national and local electrical codes for acceptable external wiring practices.
2.The bypass feed into this equipment utilizes four wires. The rectifier feed into this equipment utilizes three wires. However, the phases must be symmetrical about ground (i.e., from a Wye source) for proper equipment operation. Failure to follow these instructions will void the product warranty.
3.Material and labor for external wiring requirements are to be provided by designated personnel.
4.For external wiring, use 90°C copper wire. See the appropriate column in Tables A through M.
5.Wire ampacities are chosen from Table
6.A bypass neutral feeder must be supplied.
7.Refer to Section I of this manual for installation Instructions.
8.UPS systems not using an external battery source are supplied with internal batteries prewired to the UPS at the factory. External
|
| NOTE: Callout letter , , , and | DESCRIPTION: |
| POWER WIRING INSTALLATION NOTES |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |
|
| map to drawing | DRAWING NO: |
|
| SHEET: 1 of 17 |
|
|
| |||
|
|
| REVISION: | F |
| DATE: | 111501 |
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
| ||||||||
|
| Powerware 9330 (10 | ||||||||||
|
|
|
|
|
|
| 164201300 REV. G 061502 |