Table P. Options Cabinet Power Cable Terminations Powerware 9330 (10 kVA---20 kVA)

 

Terminal Function

Terminal

Function

 

Size of Pressure

Vendor

Tightening Torque

 

Type

 

Termination

N-M (lb-in.)

 

Screw

AC Input to UPS

L1

Phase A

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

Rectifier Transformer

 

 

 

 

 

 

 

 

L2

Phase B

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

(TB1)

 

 

 

 

 

 

 

 

 

L3

Phase C

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

 

 

 

 

 

 

 

 

 

 

 

AC Input To UPS

L1

Phase A

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

Bypass Transformer

 

 

 

 

 

 

 

 

L2

Phase B

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

(TB1)

 

 

 

 

 

 

 

 

 

 

 

Ll3

Phase C

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

 

 

 

 

 

 

 

 

 

 

N

Neutral

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

 

 

 

 

 

 

 

 

 

AC Output from

X1

Phase A

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

Output Transformer

 

 

 

 

 

 

 

 

 

 

 

 

Entrelec

2.5-2.9(22-26)

 

 

to Critical Load

X2

Phase B

1

--- #14---#0

 

Slotted

(TB1)

 

 

 

 

 

 

 

 

X3

Phase C

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

 

 

 

 

 

 

 

 

 

 

 

 

N

Neutral

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

 

 

 

 

 

 

 

 

 

Customer Ground

Ground

Ground

2

--- #14---#1/0

N/A

5.6 (50)

 

Slotted

 

 

Table Q. Options Cabinet Power Cable Terminations Powerware 9330 (25 kVA---40 kVA)

 

Terminal Function

Terminal

Function

 

Size of Pressure

Vendor

Tightening Torque

 

Type

 

Termination

N-M (lb-in.)

 

Screw

AC Input to UPS

L1

Phase A

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

Rectifier Transformer

 

 

 

 

 

 

 

 

L2

Phase B

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

(TB1)

 

 

 

 

 

 

 

 

 

L3

Phase C

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

 

 

 

 

 

 

 

 

 

 

 

AC Input To UPS

L1

Phase A

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

Bypass Transformer

 

 

 

 

 

 

 

 

L2

Phase B

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

(TB1)

 

 

 

 

 

 

 

 

 

 

Ll3

Phase C

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

 

 

 

 

 

 

 

 

 

 

N

Neutral

1

--- #4---#4/0

Entrelec

3.2-3.7(28-33)

 

6 mm

 

 

 

 

Allen

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Output from

X1

Phase A

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

Output Transformer

 

 

 

 

 

 

 

 

X2

Phase B

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

to Critical Load

 

(TB1)

 

 

 

 

 

 

 

 

X3

Phase C

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

 

Slotted

 

 

 

 

 

 

 

 

 

 

N

Neutral

1

--- #4---#4/0

Entrelec

4-6(35-52)

 

6 mm

 

 

 

 

Allen

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Customer Ground

Ground

Ground

2

--- #14---1/0

N/A

5.6 (50)

 

Slotted

 

 

NOTE: Customer ground, size 1/0, can be

DESCRIPTION:

POWER WIRING INSTALLATION NOTES

 

 

 

 

 

run in any conduit listed in Table R.

DRAWING NO:

164201300---1

 

SHEET: 11 of 17

 

 

 

 

 

 

REVISION: D

 

DATE:

053001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A---12

 

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

 

 

 

 

 

 

 

164201300 REV. G 061502

Page 182
Image 182
Powerware 9330 operation manual Sheet 11