Table O. UPS Cabinet Power Cable Terminations Powerware 9330 (25 kVA---40 kVA)

 

Terminal Function

Terminal

Function

 

Size of Pressure

Vendor

Tightening Torque

Type

 

Termination

N-M (lb-in.)

Screw

AC Input to UPS

A

Phase A

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

Rectifier and Bypass

 

 

Phoenix

3.2-3.7(28-33)

 

 

 

 

 

(TB2)

 

 

 

 

 

 

 

 

 

 

 

Entrelec

2.5-2.9(22-26)

 

(Single Input)

B

Phase B

1

--- #14---#0

Slotted

 

 

 

Phoenix

3.2-3.7(28-33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

Phase C

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

 

 

 

 

Phoenix

3.2-3.7(28-33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

Neutral

1

--- #4---#4/0

Entrelec

4-6(35-52)

6 mm

 

Phoenix

15-20(133-177)

Allen

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

A

Phase A

1

--- #2---#4/0

ABB

13.5(120)

3/16 in.

Rectifier (CB1)

 

 

 

 

 

 

B

Phase B

1

--- #2---#4/0

ABB

13.5(120)

(Dual Input)

Allen

 

 

 

 

 

 

C

Phase C

1

--- #2---#4/0

ABB

13.5(120)

 

 

 

 

 

 

 

 

 

 

AC Input To Bypass

A

Phase A

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

(TB2)

 

 

Phoenix

3.2-3.7(28-33)

 

 

 

 

 

(Dual Input)

 

 

 

 

 

 

 

B

Phase B

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

 

 

 

 

 

Phoenix

3.2-3.7(28-33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

Phase C

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

 

 

 

 

Phoenix

3.2-3.7(28-33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

Neutral

1

--- #4---#4/0

Entrelec

4-6(35-52)

6 mm

 

Phoenix

15-20(133-177)

Allen

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Output to Critical

A

Phase A

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

Load

 

 

Phoenix

3.2-3.7(28-33)

 

 

 

 

 

(Part of TB3)

 

 

 

 

 

 

 

B

Phase B

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

 

 

 

 

 

Phoenix

3.2-3.7(28-33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

Phase C

1

--- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

 

 

 

 

Phoenix

3.2-3.7(28-33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

Neutral

1

--- #4---#4/0

Entrelec

4-6(35-52)

6 mm

 

Phoenix

15-20(133-177)

Allen

 

 

 

 

 

 

 

 

 

 

 

 

DC Input from

N/A

Battery

Red Battery

N/A

N/A

N/A

Battery to UPS

 

(+)

Connector

 

 

 

 

 

N/A

Battery

Black Battery

N/A

N/A

N/A

 

 

(---)

Connector

 

 

 

 

 

 

 

 

 

 

 

 

 

External Battery

Battery

Positive

1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

Input to UPS

+

 

 

Phoenix

3.2-3.7(28-33)

 

 

 

 

(Part of TB3)

 

 

 

 

 

 

 

Battery

Negative

1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

 

 

---

Phoenix

3.2-3.7(28-33)

 

 

 

 

 

 

 

 

 

 

 

 

 

Customer Ground

Ground

Ground

2

--- #14---1/0

N/A

5.6 (50)

Slotted

NOTE: Customer ground, size 1/0, can be run in any conduit listed in Table R.

DESCRIPTION: POWER WIRING INSTALLATION NOTES

DRAWING NO:

164201300---1

 

SHEET: 10 of 17

REVISION: F

 

DATE:

111501

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

A---11

164201300 REV. G 061502

 

Page 181
Image 181
Powerware 9330 operation manual Sheet 10