13.External overcurrent protection is not provided by this product, but is required by codes. Refer to Tables A through M for wiring requirements. If an output lockable disconnect is required, it is to be supplied by designated personnel.

14.Table V lists the maximum rating for input circuit breakers.

Table V. Maximum Input Circuit Breaker Ratings

Powerware System

 

Input Voltage Rating

 

 

 

 

 

208VAC

480VAC

600VAC

DC

 

 

 

 

 

 

9330---20/10

35

15

15

35

 

 

 

 

 

9330---20/15

60

25

20

50

 

 

 

 

 

9330---20/20

70

30

25

70

 

 

 

 

 

9330---40/25

90

40

40

80

 

 

 

 

 

9330---40/30

100

50

40

100

 

 

 

 

 

9330---40/35

125

60

40

125

 

 

 

 

 

9330---40/40

125

60

50

125

 

 

 

 

 

CAUTION: To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table V in accordance with the National Electrical code, ANSI/NFPA 70.

15.When the optional Options Cabinet is used, source protection for the AC input should be treated as if you were supplying a 20 kVA three phase transformer for the

Powerware 9330 (10 kVA---20 kVA) and a 40 kVA three phase transformer for the Powerware 9330 (25 kVA---40 kVA), to allow for inrush current.

 

 

 

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

 

 

 

 

 

DRAWING NO:

164201300---1

 

SHEET: 16 of 17

 

 

 

 

 

 

REVISION: F

 

DATE:

111501

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

 

 

 

A---17

164201300 REV. G 061502

 

 

 

 

 

 

 