13.External overcurrent protection is not provided by this product, but is required by codes. Refer to Tables A through M for wiring requirements. If an output lockable disconnect is required, it is to be supplied by designated personnel.
14.Table V lists the maximum rating for input circuit breakers.
Table V. Maximum Input Circuit Breaker Ratings
Powerware System |
| Input Voltage Rating |
| ||
|
|
|
| ||
208VAC | 480VAC | 600VAC | DC | ||
| |||||
|
|
|
|
| |
35 | 15 | 15 | 35 | ||
|
|
|
|
| |
60 | 25 | 20 | 50 | ||
|
|
|
|
| |
70 | 30 | 25 | 70 | ||
|
|
|
|
| |
90 | 40 | 40 | 80 | ||
|
|
|
|
| |
100 | 50 | 40 | 100 | ||
|
|
|
|
| |
125 | 60 | 40 | 125 | ||
|
|
|
|
| |
125 | 60 | 50 | 125 | ||
|
|
|
|
|
CAUTION: To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table V in accordance with the National Electrical code, ANSI/NFPA 70.
15.When the optional Options Cabinet is used, source protection for the AC input should be treated as if you were supplying a 20 kVA three phase transformer for the
Powerware 9330 (10
|
|
| DESCRIPTION: POWER WIRING INSTALLATION NOTES |
|
|
| ||||
|
|
| DRAWING NO: |
| SHEET: 16 of 17 |
|
|
| ||
|
|
| REVISION: F |
| DATE: | 111501 |
|
|
| |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| |||||
Powerware 9330 (10 |
|
|
| |||||||
164201300 REV. G 061502 |
|
|
|
|
|
|
|