7.2.2UPS Circuit Breakers

The UPS can contain as many as 10 circuit breakers, depending on the system options. The UPS circuit breakers are described in detail in Chapter 9, “UPS Operating Instructions.”

UPS Cabinet

CB1 controls the input to the UPS rectifier, while CB2 controls the battery input to the UPS inverter. CB1 and CB2 are manually controlled.

Optional Battery Cabinet

A local battery circuit breaker controls the output of each battery cabinet, providing the ability to service each battery string individually.

Optional Options Cabinet

Input, output, and bypass circuit breakers control the flow of current to and from the installed transformers.

7.2.3Smart LOAD OFF

A smart LOAD OFF pushbutton is provided for situations where you must quickly control the UPS output. The pushbutton is located on the front of the UPS for quick access, but provides a safety feature to prevent inadvertent load dumps. The LOAD OFF pushbutton is described in detail in Chapter 9, “UPS Operating Instructions.”

7.2.4Maintenance Bypass Switch

An internal Maintenance Bypass switch is provided to completely isolate the main power processing unit of the UPS during service. The Maintenance Bypass Switch is described in detail in Chapter 9, “UPS Operating Instructions.”

7.2.5Cold Start Switch

A Cold Start switch is provided to start the UPS in Battery Mode when no commercial power is available. The Cold Start Switch is described in detail in Chapter 9, “UPS Operating Instructions.”

7.3UPS Standard Features

The UPS has many standard features that provide cost-effective and consistently reliable power protection:

7.3.1Customer Interface

Computer Interface

One serial communications port is standard on all units, and is electrically isolated from the UPS. You can use this ports to link the UPS to the features described in Chapter 12, Serial Communicationsand Chapter 13, “Remote Notification.”

Building Alarm Monitoring

You can connect your facility’s alarm system contacts to four (4) inputs in the UPS. The UPS uses these inputs to monitor your building alarms in addition to the UPS status. This feature is described further in Chapter 10, “Using Features and Options.”

7--4

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

 

164201300 REV. G 061502

Page 92
Image 92
Powerware 9330 operation manual UPS Standard Features