6.The basic environmental requirements for operation of the UPS system are:

Ambient Temperature Range:

0---40˚C (32---104˚F)

Recommended Operating Range:

20---25˚C (68---77˚F)

Maximum Relative Humidity:

95%, noncondensing

The UPS ventilation requirements are shown in Table AC.

Table AC. Air Conditioning or Ventilation Requirements

During Full Load Operation

Powerware 9330 (10 kVA-- 40 kVA)

Ratings

Input/Output Voltage

Heat Rejection*

BTU/hr ¢

1000/hr (Kg---cal/hr)

 

 

 

208/208

2.4

(0.6)

 

 

 

 

10 KVA

480/208

3.1

(0.8)

 

480/480, 600/208

3.6

(0.9)

 

 

 

 

 

208/208

3.5

(0.9)

 

 

 

 

15 KVA

480/208

4.6

(1.1)

 

 

 

 

 

480/480, 600/208

5.3

(1.3)

 

 

 

 

 

208/208

4.7

(1.2)

 

 

 

 

20 KVA

480/208, 600/208

6.1

(1.5)

 

480/480

7.1

(1.8)

 

 

 

 

 

208/208

5.9

(1.5)

 

 

 

 

25 KVA

480/208, 600/208

7.7

(1.9)

 

 

 

 

 

480/480

8.9

(2.2)

 

 

 

 

 

208/208

7.1

(1.8)

 

 

 

 

30 KVA

480/208, 600/208

9.2

(2.3)

 

480/480

10.7

(2.7)

 

 

 

 

 

208/208

8.3

(2.1)

 

 

 

 

35 KVA

480/208, 600/208

10.8

(2.7)

 

 

 

 

 

480/480

12.5

(3.1)

 

 

 

 

 

208/208

9.5

(2.4)

 

 

 

 

40 KVA

480/208, 600/208

12.4

(3.1)

 

 

 

 

 

480/480

14.3

(3.6)

 

 

 

 

 

 

 

DESCRIPTION: PHYSICAL FEATURES AND REQUIREMENTS

 

 

 

 

 

DRAWING NO:

 

164201300---3

 

SHEET:

2 of 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REVISION:

G

 

DATE:

061502

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

 

 

 

 

 

A---25

164201300 REV. G 061502

 

 

 

 

 

 

 

 

Page 195
Image 195
Powerware 9330 operation manual UPS ventilation requirements are shown in Table AC