3.2Battery Type

The following battery types are supplied in the UPS Cabinets and external Battery Cabinets. When purchasing UPS Cabinets or external Battery Cabinets without batteries, only the following types are recommended. Use of any other battery type inside Powerware cabinets will void the product warranty.

Battery Manufacturer

Yuasa, Inc.

Powersonic/Enersys

 

 

 

Battery Model

NPX–100R or NPX–100B

12GAX105

 

 

 

Battery Quantity

24

24

Powerware 9330 (10 kVA---20 kVA)

Powerware 9330 (25 kVA---40 kVA)

48

48

 

 

 

3.3Battery Installation

3.3.1Installing Internal Batteries in the UPS Cabinet

If the UPS cabinet was ordered without batteries, install the batteries in accordance with the following procedure.

WARNING:

LETHAL VOLTAGE WILL BE PRESENT WHEN PERFORMING THE STEPS IN

THIS SECTION.

1.Ensure that battery breaker CB2 is in the OFF position. If not, set breaker to OFF position.

2.Remove left front solid panel and right front vented panel from Powerware 9330 (10 kVA---20 kVA) UPS or left front solid panel and front vented panels from Powerware 9330 (25 kVA---40 kVA) UPS. Front panels are secured with magnetic latches and are removed by pulling panels straight forward to disengage magnetic latches.

3.Remove screws securing internal safety shield panels and remove panels to gain access to battery trays.

4.Remove battery trays, containing wiring and nylon straps, from the UPS cabinet.

5.Select batteries in a accordance with paragraph 3.2. Use batteries of the same age, type, and manufacturer, in each string, so UPS performance is not affected.

6.Install four batteries per tray and electrically interconnect the batteries in accordance with Figure 3---1 or 3---2.

7.Secure batteries to tray using nylon straps.

8.Reinstall battery trays into the UPS cabinet.

9.Connect battery strings in accordance with paragraph 3.4.1.

3--2

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

 

164201300 REV. G 061502

Page 58
Image 58
Powerware 9330 operation manual Battery Type, Battery Installation, Installing Internal Batteries in the UPS Cabinet