9.16Using the REMOTE EMERGENCY POWER OFF Switch
An UPS Emergency Power Off is initiated by Remote Emergency Power OFF (REPO) pushbutton switch . In an emergency, you can use this switch to control the UPS output. The REPO switch
The UPS, including Bypass, remains off until restarted.
9.16.1 To Use the REPO Switch
WARNING:
All power to the critical load is lost when this switch is activated. You should use this feature only in an emergency or when you want to
NOTE: The following instructions are for the Powerware supplied REPO switch. If a customer supplied REPO switch is used it may not activate in the same manner. If this is the case, refer to the operating instructions provided with the switch.
1.Press the REPO pushbutton switch.
The input, output, battery and bypass backfeed contactors open and the PPU is turned off immediately, without asking for verification.
CAUTION:
Do not attempt to restart the system after REPO until the cause of the emergency has been identified and cleared.
2.To restart the UPS after using the REPO pushbutton, reset the REPO switch by rotating the switch and then follow the procedure, in paragraphs 9.2 or 9.3.