Powerware 9330 operation manual Joining Additional Battery Cabinets

Models: 9330

1 246
Download 246 pages 17.16 Kb
Page 44
Image 44

14.Install side panel removed from the UPS cabinet to the right side of the Battery cabinet. Secure with screws removed from Battery cabinet.

15.When all wiring is complete, proceed to Chapter 3 and connect battery strings in accordance with instructions contained in paragraph 3.4.2.

16.Using retained hardware, reinstall shipping brackets previously removed, to front and rear of Battery cabinet with the angle facing outward.(see Figures 2---6 or 2---8).

17.Secure the front of Battery cabinet to the front of the UPS cabinet with the long flat grounding/mounting bracket from the installation kit (see Figures 2---6 or 2---8). Use hardware provided in the kit to secure the bracket.

18.Remove the top side panel mounting screw (tie/grounding bracket location in Figure 2---6) from both the Battery and UPS cabinets.

19.Secure the back of Battery cabinet to the back of the UPS cabinet with the tie/grounding bracket. Secure the bracket with the side panel mounting screws.

20.Install side panel removed from the UPS cabinet to the right side of the Battery cabinet. Secure with screws removed from Battery cabinet.

21.Secure cabinets to floor with contractor supplied hardware.

22.When all wiring is complete, proceed to Chapter 3 and connect battery strings in accordance with instructions contained in paragraph 3.4.2.

2.3.3Joining Additional Battery Cabinets

To join additional battery cabinets, perform the following steps. Refer to

Figure 2---5 for non-permanent installation or Figure 2---6 for permanent installation of the Powerware 9330 (10 kVA---20 kVA) UPS and Figure 2---7 for non-permanent installation or Figure 2---8 for permanent installation of the Powerware 9330

(25 kVA---40 kVA) UPS.

1.Roll the Battery cabinet to a spot near the right side of the previously installed Battery cabinet.

2.Remove front vented panels from the Battery cabinets. The front panels are secured with magnetic latches and are removed by pulling panels straight forward to disengage magnetic latches (see Figure 2---1).

3.Remove right side outside panel from previously installed Battery cabinet. Retain hardware.

4.Remove right side panel from new Battery cabinet. Retain hardware.

5.Install side panel removed from the new Battery cabinet to the right side of the previously installed Battery cabinet. Secure with screws removed from Battery cabinet.

6.Find the battery cable with 2-pole connector in the new Battery cabinet. Route this connector into the previously installed Battery cabinet and mate with the matching connector in the cabinet (see Figures 2---5, 2---6, 2---7, or 2---8).

7.Push the new Battery cabinet against the right side of the previously installed Battery cabinet.

2--18