Table K. Ratings & External Wiring Requirements for

Powerware 9330 (25 kVA---40 kVA)

Options Cabinet INPUT and BYPASS Transformers

 

 

 

 

Ratings 50/60 Hz

 

 

Basic unit ratings at

 

 

 

Voltage

Input

Conductor

0.7 lagging PF load

 

 

 

 

 

 

Series/

 

 

 

 

Current

Minimum

 

 

 

Input

 

Output

 

 

Model

kVA/KW

 

(Amps)

Size

 

 

40/25

25/17.5

208

 

208

69.4

4

 

 

 

 

 

 

 

 

 

 

 

40/25

25/17.5

480

 

208

30

8

 

 

 

 

 

 

 

 

 

 

 

40/25

25/17.5

600

 

208

24

10

 

 

 

 

 

 

 

 

 

 

 

40/30

30/21

208

 

208

83

2

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier

40/30

30/21

480

 

208

36

8

 

 

 

 

 

 

 

 

AC

40/30

30/21

600

 

208

28.8

10

Transformer

 

INPUT

(0.95min.PF)

40/35

35/24.5

208

 

208

97

1

 

3 , 1 gnd

 

 

 

 

 

 

 

 

40/35

35/24.5

480

 

208

42

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40/35

35/24.5

600

 

208

33.6

8

 

 

 

 

 

 

 

 

 

 

A

40/40

40/28

208

 

208

111

1/0

 

 

 

 

 

 

 

 

 

40/40

40/28

480

 

208

48

6

 

 

 

 

 

 

 

 

 

 

 

40/40

40/28

600

 

208

38.5

8

 

 

 

 

 

 

 

 

 

AC Input to UPS Bypass AC Transformer

INPUT Full Load Current

3 , 1 Neutral, 1 gnd

B

40/25

25/17.5

208

208

69.4

4

40/25

25/17.5

480

208

30

8

 

 

 

 

 

 

40/25

25/17.5

600

208

24

10

 

 

 

 

 

 

40/30

30/21

208

208

83

2

 

 

 

 

 

 

40/30

30/21

480

208

36

8

 

 

 

 

 

 

40/30

30/21

600

208

28.8

10

 

 

 

 

 

 

40/35

35/24.5

208

208

97

1

 

 

 

 

 

 

40/35

35/24.5

480

208

42

6

 

 

 

 

 

 

40/35

35/24.5

600

208

33.6

8

 

 

 

 

 

 

40/40

40/28

208

208

111

1/0

 

 

 

 

 

 

40/40

40/28

480

208

48

6

 

 

 

 

 

 

40/40

40/28

600

208

33.5

8

 

 

 

 

 

 

NOTE: Callout letter , , , and map to drawing #164201300---6