Emerson user manual 1.7LED Indicators, LED indicators summary, Introduction, Liebert AC4

Models: AC4

1 89
Download 89 pages 35.25 Kb
Page 12
Image 12
1.7LED Indicators

Introduction

1.7LED Indicators

The Liebert AC4 controller board has LED indicators that show the status of inputs, outputs and the common alarm

DS56

OUTPUT1

DS54

OUTPUT2

 

DS63

OUTPUT3

 

DS61

OUTPUT4

 

DS60

OUTPUT5

 

DS62

OUTPUT6

 

DS55

OUTPUT7

DS57

OUTPUT8

DS59

CTRLLOCK

DS58

SENLOCK

DS53

CMN ALR

 

DS52

 

MOP

DS51 LED indicators summaryManual backgroundManual backgroundManual background F PROG

DS48 Manual backgroundManual backgroundManual backgroundManual background 574 TX

DS47 Manual backgroundManual backgroundManual backgroundManual background 574 RX

DS78 Manual backgroundManual backgroundManual backgroundManual background 485 RX

DS79 Manual backgroundManual backgroundManual backgroundManual background 485 TX

DS69

 

INPUT1

DS71

 

INPUT2

DS72

 

INPUT3

 

INPUT4

DS70

 

 

INPUT5

DS67

 

DS66

 

INPUT6

DS65

 

INPUT7

DS64

 

INPUT8

Output LEDs

Status LEDs

Input LEDs

Table 2

LED indicators summary

 

 

 

 

 

 

LED Type

 

LED

Color

Description

 

 

 

 

 

EIA422

 

422 TX

Green

Liebert AC4 is transmitting information over the EIA422 port

LEDs

 

422 RX

Green

Liebert AC4 is receiving information over the EIA422 port

 

 

OUTPUT1

Green

Not used

 

 

OUTPUT2

Green

Not used

 

 

OUTPUT3

Green

Not used

 

 

OUTPUT4

Green

Not used

 

 

OUTPUT5

Green

Indicates output 1 is ON or energized

Output LEDs

OUTPUT6

Green

Indicates output 2 is ON or energized

 

 

OUTPUT7

Green

Indicates output 3 is ON or energized

 

 

OUTPUT8

Green

Indicates output 4 is ON or energized

 

 

CTRLLOCK

N/A

Not used

 

 

SENLOCK

N/A

Not used

 

 

CMN ALR

Green

Indicates output is ON or energized

 

 

MOP

Green

Indicates the microprocessor is operating properly (MOP)—must be on before

 

 

Liebert AC4 will function

 

 

 

 

 

 

FPROG

Green

Indicates firmware is being upgraded—lights up during upgrade process

Status LEDs

574 TX or 232 TX

Green

Liebert AC4 is transmitting information via the RS232 port

 

 

574 RX or 232 RX

Green

Liebert AC4 is receiving information via the RS232 port

 

 

485 RX

Green

Not used

 

 

485 TX

Green

Not used

 

 

INPUT1

Red

Not used

 

 

INPUT2

Red

Not used

 

 

INPUT3

Red

Not used

Input LEDs

INPUT4

Red

Not used

INPUT5

Red

Indicates input 1 is ON or energized

 

 

 

 

INPUT6

Red

Indicates input 2 is ON or energized

 

 

INPUT7

Red

Indicates input 3 is ON or energized

 

 

INPUT8

Red

Indicates input 4 is ON or energized

Liebert® AC4

6

Page 12