System and Control Options

7.8Setup Operation

The Liebert AC4 operation features allow you to set up a rotation sequence to alternate which devices are operating and which are placed on Standby, as well as test devices while in Standby mode and specify what to do when a Standby device goes into alarm as it is powered up. You may also specify delay times after an output changes state, directing the Liebert AC4 to wait before acknowledging inputs or turning an output on or off.

To change any operation features:

Log In and Choose Setup System

From the Main Menu, use the arrows ↑↓ to choose System and Control, then press Enter (see 7.1 Login for help).

Enter your password at the Login screen.

From the System and Control Menu, use the arrows ↑↓ to choose Setup System, then press Enter .

Select Setup Operation

From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Operation and press Enter .

Setup System Menu

SETUP INPUTS SETUP COMMON ALARM SETUP ZONES ↑↓=NEXT =SELECT

SETUP OUTPUTS SETUP SYSTEM INFO

> SETUP OPERATION

Setup Operation Menu

>AUTO SEQUENCING OFF STANDBY TESTING OFF

FAILED STANDBY N ↑↓=NEXT =SELECT

HOLD DELAY

:

10:00

RESTART

:

00:06

• Use the steps following Table 18 to access any of the Setup Operation options.

Table 18 shows the default settings for operation options: automatic sequencing, standby testing, failed standby, hold delay and restart.

Table 18 Default settings - operation features

Feature

Default

Other Options

 

 

 

AUTO SEQUENCING

OFF (Deactivated)

ON (Activated), 12h (Activated for 12-hour intervals)

STANDBY TESTING

OFF (Deactivated)

ON (Activated)

FAILED STANDBY

N (Deactivated)

Y (Activated)

HOLD DELAY

10:00 (No delay)

Any time (in minutes and seconds) from 00:00 to 99:59

RESTART

00:06 (No delay)

Any time (in minutes and seconds) from 00:00 to 99:59

43