Emerson AC4 user manual 7.2Setup System - Overview, Setup System - Setup Inputs, Setup System Menu

Models: AC4

1 89
Download 89 pages 35.25 Kb
Page 35
Image 35
7.2Setup System - Overview

System and Control Options

7.2Setup System - Overview

The Setup System screen displays six options that allow you to configure input and output devices, the common alarm, and a variety of system details, such as login password and system date and time:

Setup Inputs

Setup Common Alarm

Setup Zones

 

• Setup Outputs

Setup System Menu

 

• Setup System Info

 

 

 

 

 

 

 

 

> SETUP INPUTS

 

• Setup Operation

 

 

SETUP COMMON ALARM

7.3

Setup System - Setup Inputs

 

SETUP ZONES

 

↑↓=NEXT

=SELECT

 

 

 

 

The Liebert AC4 has four digital input points that may be configured

 

SETUP OUTPUTS

 

 

 

SETUP SYSTEM INFO

 

individually. These inputs may have a wide variety of Liebert or other

 

SETUP OPERATION

 

manufacturers’ equipment connected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To configure a digital input:

Select Input Menu

 

 

SELECT

 

INPUT

 

Log In and Choose Setup System

 

 

 

> DEVICE_1

 

NO-AL-NL

 

• From the Main Menu, use the arrows ↑↓ to choose System and

 

DEVICE_2

 

NO-AL-NL

 

 

↑↓=NEXT

 

=SELECT

 

 

Control, then press Enter (see 7.1 Login for help).

 

 

 

 

DEVICE_3 NO-AL-NL

 

• Enter your password at the Login screen.

 

 

 

DEVICE_4

 

NO-AL-NL

From the System and Control Menu, use the arrows ↑↓ to choose Setup System, then press Enter .

Select a Digital Input to Configure

From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Inputs and press Enter .

From the Select Input Menu, choose an input—for example, Device_1—and press Enter .

Table 13 shows the digital input features you may change, along with the default settings: you may change the name of the input, define it as normally open or closed, and specify it as alarmable or as an event.

Alarmable inputs may be defined as either Unlatched or Latched.

Event status allows you to monitor a digital input’s state—and use a change in state to initiate an action through an output, if desired—without triggering an alarm. Events are always Unlatched.

You may also specify a time delay before the Liebert AC4 responds to an alarm or event.

Use the steps following Table 13 to change the default settings for any digital input.

Table 13 Default settings - digital inputs

Feature

Default

Other Options

 

 

 

LABEL

DEVICE_1

Any name (up to eight characters)

NORM OPEN/CLOSE

NO (Normally open)

NC (Normally closed)

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

L (Latched) / Y (Yes)*

NL (Unlatched) / N (No)*

DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.

 

Settings - Select Input Menu

When configuring an input

 

(see Section 7.3)

(see Section 7.3.4)

Unlatched

NL (Not Latched)

N (No, not latched)

Latched

L (Latched)

Y (Yes, latched)

29

Liebert® AC4

Page 35
Image 35
Emerson AC4 user manual 7.2Setup System - Overview, Setup System - Setup Inputs, Setup System Menu, Select Input Menu