Controller board components (continued)

 

 

 

 

Introduction

 

 

 

 

 

Table 1

Controller board components (continued)

 

 

 

 

 

 

Item

Description

 

For more information, see:

 

 

 

 

 

 

 

One of four output jumpers. Each digital output has a

 

 

 

 

jumper to set the fail-safeposition of the output point when

3.2.3: Setting the Digital Output

I - Digital output

power fails. The OFF position makes the contact Normally

 

Jumpers

loss-of-power

Open (factory default). The ON position makes the contact

 

7.6.4: Configure Output for Loss of

jumper

 

Normally Closed.

 

 

Power (“Fail-Safe”)

 

 

Note: The jumper position has no effect on the contact

 

 

 

 

 

 

 

when the Liebert AC4 has power.

 

 

 

 

 

 

 

 

 

Each of the four input connections is a two-state point:

3.0:

Wiring and Connections

J - Digital input

ON/OFF (energized/de-energized).

3.2.1: Connecting Digital Inputs

connectors

An example of a field digital input is a Liebert

5.4:

View Input Status

 

 

Environmental unit’s common alarm relay output.

7.3:

Setup System - Setup Inputs

 

 

 

 

K - Digital input

Each input has an LED to indicate its status: ON/OFF

1.7:

LED Indicators

status LEDs

(energized/de-energized).

 

 

L - Serial interface

Connection for laptop or video terminal. Used for

3.4:

RS232 Connector

configuration and monitoring using the Service Terminal

connector

 

A.2:

Connecting to the Service

 

Interface. Requires a null modem cable for connectivity

(RS232/EIA574)

 

Terminal Interface

(P/N 201258P1).

 

 

 

 

 

 

 

 

M - DIP switch 1

DIP switch used for resetting password to default.

7.7.1: Change Password

 

 

 

 

N - LCD connector

Connection for the LCD on the enclosure door.

N/A

 

 

 

 

 

O - LCD contrast

Adjustment contrast for the LCD on the enclosure door.

N/A

 

adjustment

 

 

 

 

 

 

P - 24VAC power

Power connection for the controller. Requires 24VAC.

2.4:

Connect Power to the Liebert

connector

 

 

AC4

 

 

 

5