3.2.2Connecting Digital Outputs

Wiring and Connections

3.2.2Connecting Digital Outputs

The four digital outputs are found on the lower right side of the Liebert AC4 just above the input terminal blocks, as shown at right. These outputs are numbered 1 through 4.

To connect an output:

1.Turn OFF electrical power to the Liebert AC4.

2.If necessary, remove a conduit knockout to permit wire entry into the Liebert AC4 enclosure.

3.Bring the wire(s) into the Liebert AC4 enclosure through a conduit knockout or access slot.

4.Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.

5.Tighten the screw until it holds the wire snugly.

! CAUTION

To reduce the risk of fire or electric shock, do not interconnect the outputs of different class 2 circuits.

3.2.3 Setting the Digital Output Jumpers

Digital output jumpers (four)

Each digital output has an associated jumper to define its operation when power is interrupted. This puts the Liebert AC4 in a fail-safe mode and ensures proper functioning when the board has no power.

The Liebert AC4 comes from the factory with all digital output jumpers in the OFF position (normally open). The jumper setting for each digital output can be changed to ON (normally closed). The settings are shown in Table 5.

Table 5

Digital output jumper settings

 

 

 

Output status

Setting

(power loss)

OFF

Normally open

 

 

ON

Normally closed

 

 

To change the output jumper setting:

1. Find the respective loss-of-power jumper on the3.2.3 Setting the Digital Output JumpersDigital output jumper settingsManual backgroundManual backgroundManual backgroundManual background circuit board, as shown above. See Table 1 Controller board components for more information.

2.Decide whether your configuration requires the jumper to be OFF or ON.

3.Set the jumper as needed:

Set the jumper to OFF by placing the loss-of-power jumper on the middle and top pins.

Set the jumper to ON by placing the black jumper on the middle and bottom pins.