Emerson user manual 8.1Liebert AC4 Specifications, 8.0SPECIFICATIONS

Models: AC4

1 89
Download 89 pages 35.25 Kb
Page 55
Image 55
Specifications

Specifications

8.0SPECIFICATIONS

8.1Liebert AC4 Specifications

Power Requirements

24VAC ±10% of nominal

50/60 Hz

 

1.3A, 30VA

Dimensions W x D x H, in. (mm)

14-1/4 x 2-3/4 x 12

(361.95 x 69.85 x 304.8)

 

Weight (Assembled)

7.68 lbs (3.48 kg)

Enclosure Type

NEMA 1

Liquid Crystal Display (LCD)

Four line, 20 character, backlit

Mounting Surface

Building Wall or Structural Member

Ambient Operating

32°F to 104°F (0°C to 40°C)

Environment

0% RH to 95% RH (non-condensing)

Processor Specifics

 

Model

Motorola XC68HC812A4

 

 

Clock speed

16MHz

 

 

Total RAM

32Kb

 

 

Total FLASH

4M

 

 

Total EEPROM

4K

 

 

A/D Resolution (Analog IN)

12 Bit

 

 

Clock Type

Real-Time Clock

 

 

Clock battery backup type

Lithium Cell (non-replaceable)

 

 

Clock battery life

7 years, constant, no power

 

 

Communications

 

Local Communications

RS232

 

 

Agency Listings

 

UL

UL3121

 

 

CE

Yes

 

 

FCC Compliance

CFR 47 Part 15

 

 

Inputs & Outputs (Quantity)

 

Digital Inputs (4)

Dry Contact Closure

24VDC, 10 mA

 

Digital Outputs (4)

24VAC, 3A

 

 

Common Alarm Outputs (2)

24VAC, 3A

 

 

NOTE

If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.