Emerson AC4 7.6Setup System - Setup Outputs, Log In and Choose Setup System, Setup System Menu

Models: AC4

1 89
Download 89 pages 35.25 Kb
Page 40
Image 40
7.6Setup System - Setup Outputs

System and Control Options

7.6Setup System - Setup Outputs

The Liebert AC4 has four outputs that may be configured individually. These outputs correspond to the four numbered inputs. For example, Device_1 is the unit connected to Input 1 and to Output 1.

The output name is the same as the input name, as described in

7.3.1Change Label (Name of Input). To configure an output:

Log In and Choose Setup System

From the Main Menu, use the arrows ↑↓ to choose System and Control, then press Enter (see 7.1 Login for help).

Enter your password at the Login screen.

From the System and Control Menu, use the arrows ↑↓ to choose Setup System, then press Enter .

Select an Output to Configure

From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Outputs and press Enter .

From the Select Output Menu, choose an output—for example, Device_1—and press Enter .

Setup System Menu

SETUP INPUTS SETUP COMMON ALARM SETUP ZONES ↑↓=NEXT =SELECT

>SETUP OUTPUTS SETUP SYSTEM INFO SETUP OPERATION

Select Output Menu

SELECT OUTPUT

>DEVICE_1 NO-OP-E

DEVICE_2 NO-ST-E ↑↓=NEXT =SELECT

DEVICE_3 NO-NU-D DEVICE_4 NO-NU-D

Table 17 shows digital output features and their default settings: you

may define an output as normally open or normally closed, set the device’s mode—operating, standby or not used—and specify whether to disable the device when an alarm occurs.

Use the steps following Table 17 to change the default settings for any digital output.

Table 17 Default settings - digital outputs

Feature

Default

Other Options

 

 

 

NORM OPEN/CLOSE

NO (Normally open)

NC (Normally closed)

 

Outputs 1-3: OP (Operating)

OP (Operating)

MODE

ST (Standby)

Output 4: ST (Standby)

 

NU (Not Used)

 

 

 

 

 

IN ALARM

E (Enable)

D (Disable)

7.6.1Define Output as Normally Open or Normally Closed

Each output may be set up as Normally Open (NO) or Normally Closed (NC). The default setting for all output points is NO (Normally Open).

From the Setup Outputs Menu, shown at right, use the arrows ↑↓ to choose Norm Open/Close and press Enter .

To change the normal state for this output, use the arrows ↑↓ to choose the state:

NO (Normally Open)

NC (Normally Closed)

Press Enter .

Setup Outputs Menu

SETUP DEVICE_1

>NORM OPEN/CLOSE: NO

MODE: OPERATING

↑↓=NEXT =SELECT IN ALARM: ENABLE

Change State

SET TO NORMAL OPEN OR NORMAL CLOSE? NO

↑↓=NO/NC =END

Liebert® AC4

34

Page 40
Image 40
Emerson AC4 7.6Setup System - Setup Outputs, Log In and Choose Setup System, Select an Output to Configure, Change State