Emerson AC4 user manual 7.3.5Set Up Delay Time, Setup Inputs Menu, Latched / Unlatched

Models: AC4

1 89
Download 89 pages 35.25 Kb
Page 37
Image 37
7.3.5Set Up Delay Time

System and Control Options

7.3.4Set Up Alarmable Inputs in Latched or Unlatched Mode

Alarmable input points may be set up in Latched mode (Y), which requires the user to clear the Liebert AC4 alarms after an alarm has occurred, or Unlatched mode (N), in which alarms will automatically clear after a return-to-normal state. The default setting for alarmable inputs is Y (Latched). Any input defined as an event is automatically Unlatched.

An input defined as Latched does not reset automatically after an alarm. It will remain in the triggered position even after the monitored device returns to normal. After an alarm, the user must manually reset Latched inputs, as described in 7.10.1 Clear Active Alarms. This also means that any outputs linked to a Latched digital input will remain triggered until the input is manually reset.

An input defined as Unlatched will automatically track the status of the monitored device. No action by the user is required.

From the Setup Inputs Menu, choose Latched, as shown above right, and press Enter .

To change this feature, use the arrows ↑↓ to choose Y (Yes - Latched) or N (No - Unlatched), then press Enter .

NOTE: Only alarmable input points may be set up as Latched. If you attempt to set up an event as Latched, the message shown at right appears. Press the ESC key to return to the previous screen to continue configuring the digital input.

The only way to reset latched alarms is by clearing active alarms. This step is required to return latched points to their normal state. For details, see 7.10.1 Clear Active Alarms.

7.3.5Set Up Delay Time

Each input may be set up with a specified time delay between the occurrence of an alarm or event—a monitored device changes state— and any response by the Liebert AC4. This feature can prevent needless responses to transient conditions.

This delay is the amount of time that must elapse before the Liebert AC4 acknowledges the change of state in the monitored device and takes any further action, such as dialing configured pagers. The default time delay is 1 second (displayed as 00 MIN : 01 SEC).

The time delay applies only when a monitored device changes from its normal state—for example, the Liebert AC4 detects a closed contact that is defined as Normally Open.

When the monitored device returns to its normal state, the Liebert AC4 acknowledges the change of state after the delay timer ends its countdown.

Setup Inputs Menu

SETUP DEVICE_1 LABEL: DEVICE_1

NORM OPEN/CLOSE: NO

ALARM/EVENT: AL

↑↓=NEXT =SELECT

>LATCHED: N

DELAY: 00:01

Latched / Unlatched

IS ALARM

LATCHED? N

↑↓=Y/N =END

Message (if input has been defined as an event)

LATCH NOT ALLOWED WHEN IN EVENT MODE

ESC=BACK

Setup Inputs Menu

SETUP DEVICE_1 LABEL: DEVICE_1

NORM OPEN/CLOSE: NO

ALARM/EVENT: AL

↑↓=NEXT =SELECT

LATCHED: N

DELAY: 00:01

Delay Time

DELAY TIME BEFORE TRIGGER?

00 MIN : 01 SEC ↑↓=SELECT =NEXT/END

From the Setup Inputs Menu, choose Delay, as shown at right, and press Enter .

To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):

For minutes (MIN), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-99.

Press Enter to advance to seconds (SEC).

For seconds (SEC), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-59.

When finished, press Enter again.

31

Liebert® AC4

Page 37
Image 37
Emerson AC4 7.3.5Set Up Delay Time, Setup Inputs Menu, Latched / Unlatched, Message if input has been defined as an event