REV. 5 7/6/2007

Liebert Monitoring Group –Development

Input Power Supply Fail

10186

 

1

1

 

 

Input Over Voltage

10187

 

1

1

 

 

Input Under Voltage

10188

 

1

1

 

 

Bad Input Frequency

10190

 

1

1

 

 

Output Under Voltage

10218

 

1

1

 

 

Output Over Voltage

10219

 

1

1

 

 

 

Input

Holding

 

 

 

 

Data Point

Register

Register

# of Reg.

Scale

Notes /Units

Number Of Input Lines

30004

40004

1

1

Bits 12 - 15

Number Of Bypass Lines

30004

40004

1

1

Bits 4 - 7

Number Of Output Lines

30004

40004

1

1

Bits 8 - 11

Number Of SubModules

30009

40009

1

1

 

 

 

 

 

 

 

There are 16 possible Load

 

 

 

 

 

Circuits. So each bit

 

 

 

 

 

represents 1 load circuit.

 

 

 

 

 

Load Circuit 1 is bit 0, Load

 

 

 

 

 

Circuit 2 is bit 1 and so on. If

 

 

 

 

 

the bit is 1 then the Load

Load Circuit Present

30013

40013

1

 

Circuit is supported.

Nominal Power Rating

30021

40021

2

1

VA

Nominal Input Voltage

30027

40027

1

1

V

Nominal Output Voltage

30028

40028

1

1

V

Nominal Input Current

30030

40030

1

1

A

Nominal Input Frequency

30031

40031

1

10

Hz

Nominal Output Frequency

30032

40032

1

10

Hz

Nominal Power Factor

30033

40033

1

100

 

 

Nominal Battery Voltage

30034

40034

1

1

V

Auto Restart Delay

30051

40051

1

1

seconds

Device Low Battery Time

30053

40053

1

1

min

Load (Apparent Power)

30102

 

2

1

VA

Load / Capacity

30106

 

1

1

%

Input Frequency

30107

 

1

10

Hz

Output Frequency

30108

 

1

10

Hz

 

 

 

 

 

1

- 100% Charged

 

 

 

 

 

2

- Less than 100% Charged

 

 

 

 

 

3

- Charging

 

 

 

 

 

4

- Discharging

Battery Charge Status

30112

 

1

 

5

- Float Charging

 

 

6

- Equalize Charging

Battery Voltage

30113

 

1

1

V

Battery Time Remaining

30115

 

1

1

min

Battery Charge Percentage

30116

 

1

1

%

 

 

 

 

 

1

- Unknown

 

 

 

 

 

2

- Passed

 

 

 

 

 

3

- Failed

 

 

 

 

 

4

- In Progress

 

 

 

 

 

5

- System Failure

Battery Test Result

30130

 

1

1

7

- Inhibited

Input Voltage L1

30153

 

1

1

V

13

Page 16
Image 16
Emerson OpenComms-485 manual Input Holding Data Point Register # of Reg Scale